Leak Detector Sensitivity & Fixed Leak Detection Systems

Key Takeaways

  • Portable electronic leak detectors used for F-Gas compliance must have a minimum sensitivity of detecting a leak of 5 grams per year.
  • Fixed leak detection systems are legally mandatory for any F-Gas system containing 500 tCO2e or more.
  • Refrigerant gases are heavier than air; sensors for fixed systems must be placed low to the ground to detect settling gas.
  • Installing a fixed leak detection system halves the required frequency of manual statutory leak checks for systems of all sizes.
  • Fixed leak detection systems must be tested and inspected at least once every 12 months.
Last updated: July 2026

Precision in Leak Detection

To ensure that F-Gas containment strategies are actually effective, the regulations stipulate stringent technical requirements regarding the sensitivity of the equipment used. It is not enough to simply own a leak detector; the detector must be capable of finding microscopic leaks, and for large systems, manual checking alone is legally insufficient to manage the environmental risk.

Portable Electronic Detector Sensitivity

For a portable electronic leak detector to be legally compliant for use during mandatory F-Gas leak checks, it must meet specific sensitivity thresholds.

  • The 5 g/yr Rule: The detector must have a minimum sensitivity of 5 grams per year (5 g/yr). This means the device must be capable of sensing a leak so small that only 5 grams of refrigerant would escape over a full 12-month period.
  • Verification and Calibration: Electronic sensors degrade over time due to exposure to refrigerants, moisture, and background contaminants. Therefore, engineers must ensure their detectors are calibrated annually. Furthermore, before starting a leak check on a site, the engineer should functionally test the detector using a "reference leak." A reference leak is a small vial that emits a certified, exact amount of gas (e.g., exactly 5 g/yr). If the detector fails to alarm when exposed to the reference leak, it is defective and cannot be used for compliance checks.
  • Zeroing the Sensor: When using a detector in an enclosed plant room where background levels of F-Gas might be slightly elevated (but below dangerous levels), the engineer must "zero" the detector to the ambient air. This allows the device to ignore the background noise and only alarm when it encounters a higher concentration of gas near a leaking joint.

Fixed Leak Detection Systems

While portable detectors are used during scheduled maintenance, they offer zero protection in the months between visits. A massive pipe rupture could vent an entire system's charge into the atmosphere in minutes. To address this risk for heavily polluting systems, continuous automated monitoring is employed.

Mandatory Thresholds

The installation of a Fixed Leak Detection System is legally mandatory for any F-Gas circuit containing 500 tonnes CO2 equivalent (tCO2e) or more. For a gas with a high GWP like R404A, this threshold is reached at just 127 kg. For a large supermarket or an industrial cold store, this is a relatively common charge size.

Operators can voluntarily install fixed systems on smaller equipment (between 5 and 500 tCO2e) to benefit from reduced manual inspection frequencies, but at 500 tCO2e, it ceases to be optional.

Sensor Placement and Operation

Fixed leak detection systems consist of a central control panel wired to multiple remote sensors scattered throughout the facility.

  • Gas Density: Halocarbon F-Gases (HFCs, HFOs) are significantly heavier than air. When they leak, they sink and pool on the floor or in trenches. Therefore, sensors must be placed close to the ground, typically 200 mm to 300 mm above floor level.
  • Airflow Considerations: Sensors must not be placed directly in the path of extraction fans or strong drafts, which would blow the leaking gas away before it can be detected. They must be positioned near the components most likely to leak, such as compressor packs, liquid receivers, and valve stations.

Alarm Requirements

When a fixed sensor detects a concentration of F-Gas that indicates a leak, it must immediately trigger an alarm.

  • The regulations require the alarm to alert the operator or a supervisory center so that immediate corrective action can be taken.
  • The alarm usually triggers both a high-decibel audible siren and flashing visual beacons inside the plant room to warn anyone entering that the atmosphere may be compromised (refrigerants displace oxygen and pose an asphyxiation hazard).

Impact on Inspection Intervals

Because a fixed system provides 24/7 monitoring, the F-Gas regulations reward the operator by cutting the required frequency of manual leak checks in half.

  • A 50 tCO2e system (normally checked every 6 months) only requires a manual check every 12 months.
  • A 500 tCO2e system (normally checked every 3 months) only requires a manual check every 6 months.

Note: The fixed leak detection system itself is a critical piece of safety equipment. The regulations mandate that the fixed system's sensors and alarms must be tested and inspected for proper operation at least once every 12 months, and the results of this test must be recorded in the site's F-Gas logbook.

Test Your Knowledge

What is the minimum required sensitivity for a portable electronic leak detector used during mandatory F-Gas checks?

A
B
C
D
Test Your Knowledge

At what system charge size does the installation of a fixed leak detection system become legally mandatory?

A
B
C
D
Test Your Knowledge

Where should the sensors for a fixed leak detection system generally be positioned in a plant room?

A
B
C
D