6.1 Psychrometric Principles & Air-Conditioning Processes
Key Takeaways
- Moist air obeys Dalton's law of partial pressures ($p = p_a + p_w$), where the humidity ratio $\omega = 0.622 \frac{p_w}{p - p_w}$ quantifies moisture mass per unit mass of dry air.
- Sensible heating and cooling occur at a constant humidity ratio ($\Delta \omega = 0$), governed by the standard air heat rate formula $\dot{q}_s = 1.08 \times CFM \times \Delta T$ in US Customary units ($1.23 \times \dot{V}_{L/s} \times \Delta T$ in SI units).
- Cooling with dehumidification occurs when coil surface temperatures fall below the entering air dew point, characterized by the Apparatus Dew Point (ADP) and coil Bypass Factor ($BF$).
- The total heat transfer rate across any psychrometric process is proportional to the enthalpy difference: $\dot{q}_t = 4.5 \times CFM \times \Delta h$ in US Customary units ($1.20 \times \dot{V}_{L/s} \times \Delta h$ in SI units), with the Sensible Heat Ratio defined as $SHR = \dot{q}_s / \dot{q}_t$.
- Adiabatic mixing of two moist air streams follows conservation of dry air mass and enthalpy, forming a mixed state point that lies on the straight line connecting the entering states according to the lever rule: $\frac{T_{db,3} - T_{db,1}}{T_{db,2} - T_{db,3}} = \frac{\dot{m}_{da,2}}{\dot{m}_{da,1}}$.
Psychrometric Principles & Air-Conditioning Processes
Psychrometrics is the branch of thermodynamics dedicated to atmospheric air combined with water vapor. It serves as the foundational core for heating, ventilating, air-conditioning, and refrigeration (HVAC&R) system design. On the NCEES PE Mechanical exam, psychrometric analysis is essential for evaluating air handling unit (AHU) performance, sizing direct expansion (DX) and chilled water cooling coils, determining required supply airflow rates, and analyzing mixing plenums and evaporative coolers.
1. Thermodynamic Properties of Moist Air & Dalton's Law
Atmospheric moist air is treated as a binary mixture of dry air (a pseudo-pure gas with apparent molecular weight $M_a = 28.966\text{ lbm/lbmol} = 28.966\text{ kg/kmol}$) and water vapor ($M_w = 18.015\text{ lbm/lbmol} = 18.015\text{ kg/kmol}$). Under typical HVAC operating ranges (temperatures from $-40^\circ\text{F}$ to $140^\circ\text{F}$ and pressures near atmospheric), both dry air and water vapor behave in close accordance with the ideal gas law ($p V = m R T$).
+-----------------------------------------------------------------------------------------+
| MOIST AIR CONSTITUENTS & DALTON'S LAW |
| |
| Total Barometric Pressure: p = p_a + p_w |
| |
| - Dry Air Partial Pressure: p_a = \frac{m_a R_a T}{V} |
| - Water Vapor Partial Press: p_w = \frac{m_w R_w T}{V} |
| - Standard Atmospheric Press: p = 14.696 psia = 29.921 in. Hg = 101.325 kPa |
+-----------------------------------------------------------------------------------------+
Primary Psychrometric Variables
- Dry-Bulb Temperature ($T_{db}$ or $T$): The true thermodynamic temperature of the moist air mixture measured by an ordinary, unshielded thermometer unaffected by radiation or moisture.
- Wet-Bulb Temperature ($T_{wb}$ or $T^*$): The equilibrium temperature registered by an accurate thermometer whose sensor is covered by a wetted wick and exposed to rapid airflow ($> 900\text{ FPM}$). At saturation (100% relative humidity), dry-bulb, wet-bulb, and dew-point temperatures are all identical: $T_{db} = T_{wb} = T_{dp}$.
- Dew-Point Temperature ($T_{dp}$): The temperature at which water vapor in moist air begins to condense when the mixture is cooled at constant moisture content ($\omega = \text{const}$) and constant total pressure ($p = \text{const}$). $T_{dp}$ is strictly a function of the water vapor partial pressure $p_w$, satisfying $p_w = p_{ws}(T_{dp})$, where $p_{ws}$ is the saturation pressure of water.
- Relative Humidity ($\phi$): The ratio of the actual water vapor partial pressure $p_w$ to the saturation pressure $p_{ws}$ at the same dry-bulb temperature:
- Humidity Ratio / Specific Humidity ($\omega$ or $W$): The ratio of the mass of water vapor ($m_w$) to the mass of dry air ($m_{da}$): In US Customary units, moisture content is frequently expressed in grains of moisture per pound of dry air ($1\text{ lbm} = 7,000\text{ grains}$):
- Specific Volume ($v$): The total volume of the moist air mixture per unit mass of dry air: Where $R_a = 53.35\text{ ft}\cdot\text{lbf}/(\text{lbm}\cdot^\circ\text{R}) = 0.2870\text{ kJ}/(\text{kg}\cdot\text{K})$ and $T$ is absolute temperature ($^\circ\text{R}$ or $\text{K}$).
- Specific Enthalpy ($h$): The total thermal energy of the moist air mixture per unit mass of dry air, using $0^\circ\text{F}$ (or $0^\circ\text{C}$) dry air and $32^\circ\text{F}$ liquid water as reference states:
- US Customary Units:
- SI Units:
2. Navigating the Standard Psychrometric Chart
The standard sea-level psychrometric chart ($p = 14.696\text{ psia} = 101.325\text{ kPa}$) plots thermodynamic properties on a 2D coordinate system.
+-----------------------------------------------------------------------------------------+
| PSYCHROMETRIC CHART GEOMETRY & AXES |
| |
| Humidity Ratio (\omega) / Enthalpy (h) |
| ^ |
| | / Constant Volume (v) |
| | Saturation / |
| | Curve / |
| | (\phi=100%)/ Constant Wet-Bulb (T_wb) |
| | ,-''''' / / & Specific Enthalpy (h) |
| | _,-' / ,' |
| | _,-' / ,' |
| | _,-' / ,' |
| | _,-' /,' --- Constant Relative |
| | _,-' /' Humidity (\phi = 50%) |
| | _,-' / |
| | _,-' / |
| | _,-' / |
| | _,-' / |
| +----+-----------------------------------+--------------------------------------> |
| Dew Point (T_dp) Dry-Bulb Temperature (T_db) |
+-----------------------------------------------------------------------------------------+
| Property | Chart Orientation & Geometry |
|---|---|
| Dry-Bulb Temperature ($T_{db}$) | Vertical lines originating along the horizontal baseline axis |
| Humidity Ratio ($\omega$ / $W$) | Horizontal lines reading onto the right-hand vertical axis |
| Saturation Curve ($\phi = 100%$) | Boundary curve along the upper-left envelope of the chart |
| Relative Humidity ($\phi$) | Non-linear curved lines paralleling the outer saturation curve |
| Wet-Bulb Temperature ($T_{wb}$) | Moderately steep diagonal lines extending downward to the right |
| Specific Enthalpy ($h$) | Diagonal lines nearly parallel to lines of constant wet-bulb temperature |
| Specific Volume ($v$) | Steeply pitched straight diagonal lines |
[!IMPORTANT] Altitude and Barometric Corrections: Standard psychrometric charts are valid only at sea level ($14.696\text{ psia} = 101.325\text{ kPa}$). At higher elevations (e.g., Denver at $5,000\text{ ft}$, $p \approx 12.23\text{ psia}$), atmospheric pressure decreases, causing the humidity ratio $\omega = 0.622 \frac{p_w}{p - p_w}$ and specific volume $v$ to increase for the same dry-bulb temperature and dew point. Always use an elevation-corrected chart or Dalton's law formulas when solving non-sea-level problems.
3. Core Psychrometric Air-Conditioning Processes
Every HVAC cycle decomposes into basic linear or multi-step psychrometric transformations on the chart.
+-----------------------------------------------------------------------------------------+
| SUMMARY OF CORE PSYCHROMETRIC PROCESSES |
| |
| [2] Humidification Only (\Delta T_db = 0, \omega \uparrow) |
| ^ |
| [6] Evaporative Cooling | [1] Sensible Heating |
| (Adiabatic Saturation) | (\omega = const, T_db \uparrow) |
| \ | / |
| \ | / |
| \ | / |
| <---------------------- [0] ----------------------> |
| / State Point \ |
| / | \ |
| / | \ |
| [4] Cooling & Dehumidification | [5] Chemical Dehumidification |
| (T_db \downarrow, \omega \downarrow) v (T_db \uparrow, \omega \downarrow) |
| [3] Dehumidification Only (\Delta T_db = 0, \omega \downarrow) |
+-----------------------------------------------------------------------------------------+
1. Sensible Heating and Cooling
Sensible processes occur when moist air passes over a heating or cooling coil whose surface temperature remains above the dew-point temperature of the entering air ($T_{\text{surface}} > T_{dp}$). Moisture is neither added nor removed ($\Delta \omega = 0$).
Applying standard sea-level air properties ($\rho = 0.075\text{ lbm/ft}^3$, $c_{pa} = 0.240\text{ BTU/lbm}\cdot^\circ\text{F}$):
In SI units ($\rho = 1.204\text{ kg/m}^3$, $c_{pa} = 1.006\text{ kJ/kg}\cdot\text{K}$):
2. Cooling and Dehumidification
When air passes over a cooling coil whose effective surface temperature is below the entering air dew point ($T_{\text{coil}} < T_{dp}$), moisture condenses out of the air stream. The process line on the psychrometric chart curves downward and leftward toward the Apparatus Dew Point (ADP), which represents the effective coil surface temperature on the saturation curve ($\phi = 100%$).
+-----------------------------------------------------------------------------------------+
| COIL BYPASS FACTOR & APPARATUS DEW POINT |
| |
| Saturation Curve |
| ,-' |
| ,' |
| ,' [ADP] (T_adp, \omega_adp) |
| / \ |
| / \______ [Leaving Air Point: 2] (T_db,2, \omega_2) |
| / \ |
| / \______ [Entering Air Point: 1] (T_db,1, \omega_1) |
| / |
+-----------------------------------------------------------------------------------------+
- Bypass Factor ($BF$): The fraction of total airflow that passes through the cooling coil completely unconditioned:
- Contact Factor ($CF$): The fraction of total air that comes into direct contact with the coil surface and achieves thermal equilibrium at the ADP:
3. Latent Heat and Total Heat Equations
- Latent Heat Transfer Rate (Moisture Addition or Removal): When moisture is given in grains per pound of dry air ($W_{gr}$):
- Total Heat Transfer Rate (Enthalpy Method): In SI units:
4. Sensible Heat Ratio (SHR)
The ratio of sensible heat removal rate to total heat removal rate:
- Room Sensible Heat Ratio (RSHR): $\frac{\dot{q}{s,\text{room}}}{\dot{q}{t,\text{room}}}$, defining the slope of the condition line between the supply air state and the room design state.
- Grand Sensible Heat Ratio (GSHR): $\frac{\dot{q}{s,\text{total}}}{\dot{q}{t,\text{total}}}$, defining the slope of the process line across the central cooling coil.
4. Adiabatic Mixing of Two Air Streams
In standard air handling systems, outdoor ventilation air (Stream 1) mixes adiabatically with recirculated return air (Stream 2) to produce mixed air (Stream 3) entering the conditioning coils.
+-----------------------------------------------------------------------------------------+
| ADIABATIC AIR STREAM MIXING SCHEMATIC |
| |
| Outdoor Air (Stream 1) ---> [ MIXING ] ---> Mixed Air (Stream 3) |
| (m_1, T_1, \omega_1, h_1) [ PLENUM ] (m_3 = m_1 + m_2, T_3, \omega_3, h_3) |
| Return Air (Stream 2) ---> [ ] |
| (m_2, T_2, \omega_2, h_2) |
+-----------------------------------------------------------------------------------------+
Conservation Governing Equations:
- Dry Air Mass Balance: $\dot{m}{da,3} = \dot{m}{da,1} + \dot{m}_{da,2}$
- Energy Balance: $\dot{m}{da,1} h_1 + \dot{m}{da,2} h_2 = \dot{m}{da,3} h_3 \implies h_3 = \frac{\dot{m}{da,1} h_1 + \dot{m}{da,2} h_2}{\dot{m}{da,1} + \dot{m}_{da,2}}$
- Moisture Balance: $\dot{m}{da,1} \omega_1 + \dot{m}{da,2} \omega_2 = \dot{m}{da,3} \omega_3 \implies \omega_3 = \frac{\dot{m}{da,1} \omega_1 + \dot{m}{da,2} \omega_2}{\dot{m}{da,1} + \dot{m}_{da,2}}$
- Dry-Bulb Temperature Approximation (Volumetric Basis):
The Psychrometric Lever Rule
The mixed state point (Point 3) lies on the straight line connecting Point 1 and Point 2 on the psychrometric chart. The line segment lengths are inversely proportional to the mass flow rates:
5. Evaporative Cooling (Adiabatic Saturation)
In direct evaporative cooling (swamp coolers), unsaturated air passes through a wetted porous medium without external heat transfer ($\dot{q} = 0$).
- The sensible heat of the air stream provides the latent heat required to vaporize the liquid water.
- Thermodynamic Path: The process moves upward and leftward along a constant wet-bulb temperature / constant enthalpy line ($T_{wb} = \text{const}$, $h \approx \text{const}$).
- Outcome: Dry-bulb temperature decreases ($T_{db} \downarrow$), while humidity ratio increases ($\omega \uparrow$) and relative humidity increases ($\phi \uparrow$).
- Direct Evaporative Saturation Effectiveness ($\epsilon_{\text{evap}}$):
- Indirect Evaporative Cooling: Primary air passes through dry channels of a heat exchanger while secondary air is cooled evaporatively in adjacent wet channels, providing sensible cooling at constant moisture content ($\omega = \text{const}$) without adding humidity to the supply air.
6. Step-by-Step Worked Engineering Problem
Problem Statement
An air handling unit (AHU) serves a commercial office zone. The space design condition is $75.0^\circ\text{F } T_{db}$ and $50%\text{ RH}$ ($h_{\text{room}} = 28.10\text{ BTU/lbm}{da}, \omega{\text{room}} = 0.00925\text{ lbm/lbm}_{da}$). The total supply airflow rate is $12,000\text{ CFM}$.
- Outdoor Air (OA): $3,000\text{ CFM}$ at $95.0^\circ\text{F } T_{db}$ and $76.0^\circ\text{F } T_{wb}$ ($h_{\text{OA}} = 39.40\text{ BTU/lbm}{da}, \omega{\text{OA}} = 0.01480\text{ lbm/lbm}_{da}$).
- Return Air (RA): $9,000\text{ CFM}$ at room conditions ($75.0^\circ\text{F } T_{db}, 50%\text{ RH}$).
- The mixed air enters a chilled water cooling coil with an Apparatus Dew Point (ADP) of $52.0^\circ\text{F}$ ($h_{\text{ADP}} = 21.40\text{ BTU/lbm}{da}, \omega{\text{ADP}} = 0.00820\text{ lbm/lbm}_{da}$) and a Bypass Factor ($BF$) of $0.12$.
Calculate:
- The mixed air dry-bulb temperature ($T_{db,m}$), enthalpy ($h_m$), and humidity ratio ($\omega_m$).
- The leaving air dry-bulb temperature ($T_{db,L}$) and enthalpy ($h_L$).
- The total cooling coil capacity required in Tons of Refrigeration (TR).
- The coil Sensible Heat Ratio (SHR).
+-----------------------------------------------------------------------------------------+
| AHU COIL CALCULATION SCHEMATIC |
| |
| OA: 3,000 CFM, 95°F ----> [ MIXING ] |
| [ PLENUM ] ---> MIXED AIR ---> [ COOLING COIL ] ---> SUPPLY |
| RA: 9,000 CFM, 75°F ----> [ ] (T_m, h_m) [ ADP = 52°F ] (T_L, h_L)|
| [ BF = 0.12 ] |
+-----------------------------------------------------------------------------------------+
Step 1: Mixed Air Properties
Fraction of Outdoor Air: $x_{OA} = \frac{3,000}{12,000} = 0.25$, Fraction of Return Air: $x_{RA} = \frac{9,000}{12,000} = 0.75$.
Step 2: Leaving Air Conditions from Coil Bypass Factor
Step 3: Total Cooling Coil Capacity
Step 4: Sensible Coil Capacity & SHR
7. Common Exam Traps & PE Pro-Tips
- Trap 1 — Using Standard Air Multipliers at High Elevation: The constants $1.08$, $4840$, and $4.5$ are valid only at standard sea-level air density ($\rho = 0.075\text{ lbm/ft}^3$, $p = 14.696\text{ psia}$). At non-standard altitudes, you must calculate mass flow directly using $\dot{m} = \rho \dot{V} = \frac{p \dot{V}}{R_a T}$ and apply $\dot{q}_s = \dot{m} c_p \Delta T$ and $\dot{q}_t = \dot{m} \Delta h$.
- Trap 2 — Misinterpreting Apparatus Dew Point Location: The Apparatus Dew Point (ADP) is always located on the saturation curve ($\phi = 100%$). It represents the effective coil surface temperature if the coil had a bypass factor of zero ($BF = 0$). Leaving air dry-bulb is always higher than the ADP whenever $BF > 0$.
- Trap 3 — Mixing Moisture Units: When computing latent heat with humidity ratio $\omega$ in $\text{lbm}w/\text{lbm}{da}$, use the $4840$ constant. When using moisture in grains per pound ($W_{gr}$), use the $0.69$ constant ($4840 / 7000 = 0.691$).
At standard atmospheric pressure (14.696 psia), moist air has a dry-bulb temperature of 82°F and a water vapor partial pressure of 0.285 psia. What is the humidity ratio of this air mixture?
An air stream of 5,000 CFM at 92°F dry-bulb and 40% RH mixes adiabatically with 10,000 CFM of return air at 74°F dry-bulb and 50% RH. Assuming standard atmospheric pressure, what is the resulting mixed air dry-bulb temperature?
A cooling coil receives 10,000 CFM of moist air at an entering enthalpy of 35.0 BTU/lbm_da and discharges the air at a leaving enthalpy of 25.0 BTU/lbm_da. If the sensible cooling heat removal rate is 315,000 BTU/hr, what is the coil Sensible Heat Ratio (SHR)?
In a direct evaporative cooler operating with an adiabatic saturation process, what happens to the specific enthalpy and relative humidity of the air as it passes through the wetted media?