8.4 Arc Flash Hazards, Personal Protective Equipment & Rubber Insulating Gloves

Key Takeaways

  • Arc flash hazards release extreme plasma temperatures (up to 35,000°F), explosive pressure waves (arc blast), and UV radiation, with an incident energy of 1.2 cal/cm² triggering second-degree skin burns.
  • Under 29 CFR 1910.137 and ASTM D120, rubber insulating gloves are classified into six voltage classes (Class 00 rated for 500V up to Class 4 rated for 36,000V).
  • Leather protector gloves must always be worn directly over rubber insulating gloves to provide vital physical protection against mechanical punctures, cuts, tears, and abrasions.
  • Under 1910.137(c)(2)(ii), rubber insulating gloves must be inspected for damage before each day's use and immediately after any incident suspected of causing damage, and gloves must be given an air test along with that inspection.
  • Under 29 CFR 1910.137(c)(2)(viii) and Table I-5, rubber insulating gloves must be electrically tested before first issue and every 6 months thereafter, while sleeves are tested before first issue and every 12 months thereafter.
Last updated: August 2026

8.4 Arc Flash Hazards, Personal Protective Equipment & Rubber Insulating Gloves

Arc Flash and Arc Blast Physics

An Arc Flash is a dangerous explosive release of energy caused by an electric arc fault through air between phase conductors or between phase conductors and ground. Arc faults are typically initiated by accidental tool contact, dust accumulation, insulation breakdown, or equipment failure.

Severe Hazards Associated with Arc Flash Events:

  • Extreme Temperatures: Arc temperatures can reach 35,000°F (19,400°C)—four times hotter than the surface of the sun—instantaneously vaporizing copper conductors and steel enclosures.
  • Arc Blast Pressure Wave: Rapid thermal expansion of air creates explosive blast pressure waves exceeding 2,000 lbs/sq ft, capable of knocking technicians off ladders and destroying switchgear walls.
  • Molten Metal Shrapnel: Vaporized copper expands 67,000 times its solid volume, blasting molten droplets and metal shrapnel outward at speeds exceeding 700 mph.
  • Intense UV & Acoustic Energy: High-intensity ultraviolet radiation causes instantaneous blindness, accompanied by sound pressure levels exceeding 160 decibels (dB), causing permanent eardrum rupture.

Incident Energy and Arc Flash Boundaries

Incident Energy is the amount of thermal energy impressed on a surface at a specified distance from an electrical arc fault, measured in calories per square centimeter ($cal/cm^2$).

The Second-Degree Burn Threshold

In electrical safety standards (NFPA 70E / OSHA 1910.335), an incident energy level of $1.2\text{ cal/cm}^2$ represents the exact threshold for the onset of a second-degree burn on unprotected human skin (equivalent to holding a finger in the flame of a cigarette lighter for one second).

The Arc Flash Boundary

The Arc Flash Boundary is defined as the physical distance from an arc source at which potential incident energy equals $1.2\text{ cal/cm}^2$. Anyone working inside the Arc Flash Boundary MUST wear arc-rated personal protective equipment (PPE).


Electrical Personal Protective Equipment (1910.335 & NFPA 70E)

Under 29 CFR 1910.335, employees working in areas where electrical hazards exist must be provided with, and use, protective equipment designed and constructed for the specific body part to be protected.

Head, Eye, and Body Protection Criteria:

  • Non-Conductive Head Protection: Class E hard hats (tested to 20,000 volts) are required for high-voltage shock exposure. Class G (2,200V) hard hats provide limited protection. Class C (conductive) hard hats are strictly prohibited.
  • Eye & Face Protection: Arc-rated face shields combined with safety glasses must be worn whenever there is an arc flash hazard. Face shields must be rated for the incident energy ($cal/cm^2$).
  • Arc-Rated (FR) Clothing: Flame-resistant clothing (NOMEX, treated cotton) rated in $cal/cm^2$ must cover all exposed skin. Outer garments must match or exceed the PPE category requirement (Categories 1 through 4, ranging from $4\ cal/cm^2$ to $40\ cal/cm^2$).
  • Undergarment Restrictions: Undergarments made of synthetic materials (nylon, polyester, rayon, spandex) are strictly prohibited under 1910.335 because they melt directly into human skin during an arc flash thermal event. Only 100% natural fibers (cotton, wool) are permitted.

Rubber Insulating Gloves: Voltage Classification (1910.137 / ASTM D120)

Rubber insulating gloves are the primary defense against electrical shock. Governed by 29 CFR 1910.137 and ASTM D120, rubber gloves are divided into six distinct voltage classes, designated by color-coded cuffs and labels:

Glove ClassColor LabelMaximum Use Voltage (AC)Proof Test Voltage (AC)
Class 00Beige500 Volts2,500 Volts
Class 0Red1,000 Volts5,000 Volts
Class 1White7,500 Volts10,000 Volts
Class 2Yellow17,000 Volts20,000 Volts
Class 3Green26,500 Volts30,000 Volts
Class 4Orange36,000 Volts40,000 Volts
MEMORY TIP FOR GLOVE CLASSES:
Class 00 = 500V (Beige)  | Class 0 = 1,000V (Red)   | Class 1 = 7,500V (White)
Class 2  = 17,000V (Yel) | Class 3 = 26,500V (Grn) | Class 4 = 36,000V (Org)

Mandatory Leather Protectors (1910.137(c)(2)(vii))

Rubber insulating gloves are highly vulnerable to mechanical damage. Under 29 CFR 1910.137(c)(2)(vii), leather protector gloves must ALWAYS be worn over rubber insulating gloves.

  • Mechanical Defense: Leather protectors protect the soft rubber underneath from punctures, abrasions, metal burrs, cuts, and tears.
  • Dielectric Function: Leather protectors offer zero electrical insulation by themselves; their sole function is mechanical preservation of the rubber dielectric barrier.
  • Cuff Clearance: a minimum distance must be maintained between the cuff of the leather protector and the cuff of the rubber glove so that surface tracking cannot bridge the insulation. The required gap increases with the voltage class and is specified in the consensus standard ASTM F496 (in-service care of insulating gloves and sleeves) rather than in the text of 1910.137 itself.

Daily Inspection and Air Testing Protocols (1910.137(c)(2)(ii))

Rubber insulating gloves must be inspected for flaws before each day's use and immediately following any situation where damage is suspected.

Air Testing Procedure

In addition to visual inspection, rubber gloves must undergo a mandatory air test prior to daily use:

  1. Manual Air Inflation: The cuff of the glove is rolled tightly toward the fingers to trap air inside, or a portable manual air pump/glove inflator is utilized.
  2. Pinch & Listen: The inflated glove is held near the technician's ear and cheek to check for escaping air, listening for faint hissing sounds and feeling for air leakage.
  3. Inspection of Stretched Rubber: Inflation stretches the rubber, making microscopic pinholes, ozone cuts, embedded wood splinters, or chemical cracks readily visible.
  4. Rejection: Any glove exhibiting air leakage, ozone checking, swelling, or embedded debris must be removed from service immediately.

Periodic Laboratory Electrical Re-Testing (1910.137(c)(2)(viii))

Visual and air testing cannot verify the ongoing dielectric breakdown strength of rubber insulation. OSHA standard 29 CFR 1910.137(c)(2)(viii) mandates periodic laboratory electrical re-testing:

Mandatory Testing Intervals:

  • Gloves In Active Service: Must be electrically re-tested in an accredited laboratory at least once every 6 months.
  • Tested but Not Yet Issued: insulating equipment that has been electrically tested but not issued for service may not be placed into service unless it has been electrically tested within the previous 12 months.
  • Sleeves: rubber insulating sleeves follow a longer cycle - before first issue and every 12 months thereafter.
  • Additional triggers: retesting is also required upon any indication that the insulating value is suspect, after repair, and - for gloves - after any use without protectors.
  • Stamp Requirements: Upon passing laboratory high-voltage proof testing, the glove cuff must be stamped with the test date or re-test expiration date.

Storage and Care Directives

Rubber insulating equipment must be stored in a manner that prevents environmental degradation:

  • Storage Location: Stored flat or cuff-down inside heavy canvas glove storage bags.
  • Prohibited Conditions: Must be kept away from direct sunlight (UV degradation), extreme heat, ozone (electric motors/transformers), moisture, and petroleum-based solvents/oils.
Loading diagram...
Rubber Insulating Glove Voltage Classes & Maintenance Testing Lifecycle
Test Your Knowledge

Under 29 CFR 1910.137(c)(2)(viii) and ASTM D120 standards, what is the MAXIMUM allowable interval for periodic laboratory electrical re-testing of rubber insulating gloves actively placed in service?

A
B
C
D
Test Your Knowledge

What is the Maximum Use Voltage (AC) rating for a Class 0 rubber insulating glove under 29 CFR 1910.137 and ASTM D120?

A
B
C
D
Test Your Knowledge

Why must leather protector gloves ALWAYS be worn over rubber insulating gloves during electrical work?

A
B
C
D
Test Your Knowledge

What incident energy level (cal/cm²) represents the standard threshold for the onset of a second-degree burn on unprotected human skin, establishing the Arc Flash Boundary?

A
B
C
D