6.2 Pressure Control Devices & Governors

Key Takeaways

  • NFPA 1901 mandates that pressure control systems must limit discharge pressure spikes to no more than 30 psi (200 kPa) above set pressure within 3 to 10 seconds of line shutdown.
  • Spring-loaded and pilot-operated automatic pressure relief valves operate by bypassing excess discharge water back to the pump intake manifold.
  • Electronic pressure governors (EPG) monitor pump discharge pressure via pressure transducers and adjust engine ECM fueling to maintain set operating pressure or RPM.
  • Pressure mode on an EPG automatically compensates for line shutdowns by reducing engine RPM, whereas RPM mode maintains fixed engine speed regardless of discharge changes.
  • NFPA 1901 requires discharge valves 3 inches (75 mm) or larger to be equipped with slow-operating mechanisms requiring at least 3 seconds to fully open or close to prevent water hammer.
Last updated: July 2026

6.2 Pressure Control Devices & Governors

Fireground operations are inherently dynamic. As handline nozzles are opened, closed, or gated down, the flow demand on a fire pump shifts rapidly. When a discharge nozzle flowing 200 GPM is suddenly shut off, the momentum of moving water instantly redirects into the remaining discharge lines, creating severe pressure surges. NFPA 1901 (Standard for Automotive Fire Apparatus) mandates that fire pumps equipped with discharge valves 1.5 inches or larger must feature an automatic pressure control system. This system must control discharge pressure surges to ensure pressure increases do not exceed 30 psi (200 kPa) above the set working pressure within 3 to 10 seconds following rapid valve closure.


Mechanical Pressure Relief Valves

Mechanical pressure relief valves protect pump components and hose lines by diverting excess pressurized water from the discharge side of the pump back to the intake side whenever system pressure exceeds a preset limit.

Spring-Loaded Relief Valves

The simplest mechanical pressure control device is the spring-loaded relief valve. It consists of a heavy adjustable coil spring holding a valve disk tightly against an internal seat between the discharge manifold and the intake manifold.

  • Operation: The driver/operator turns an adjusting handwheel to compress the spring to a desired pressure setting (e.g., 150 psi). As long as system pressure remains below 150 psi, spring force holds the valve closed.
  • Relief Action: If a line is closed and discharge pressure rises to 165 psi, the hydraulic pressure overcomes spring tension, pushing the valve disk off its seat. Water dumps back into the pump intake manifold until pressure drops back to 150 psi, at which point the spring reseats the disk.

Pilot-Operated Relief Valves

Modern mechanical relief systems utilize pilot-operated pressure relief valves, which offer faster response times and higher flow capacities than direct spring-loaded designs. A pilot-operated assembly consists of two primary components: a small pilot valve (control element) and a large main relief valve (operating element).

  1. Pilot Valve: A sensitive, spring-loaded needle valve connected to the discharge manifold. The operator sets the desired pressure on the pilot valve handwheel.
  2. Main Valve: Held closed by a balanced chamber filled with discharge water fed through an internal sensing line.
  3. Surge Activation: When discharge pressure exceeds the pilot valve setting, the pilot needle opens, venting pressure from above the main valve diaphragm/piston. This pressure drop creates a pressure differential, causing the main valve to open rapidly and bypass large volumes of water from discharge to intake.
  4. Reset: Once discharge pressure stabilizes below the set point, the pilot valve closes, water pressure rebuilds above the main valve piston, and the main valve smoothly reseats.

Electronic Pressure Governors (EPG)

Modern fire apparatus equipped with electronically controlled diesel engines utilize Electronic Pressure Governors (EPG) instead of mechanical relief valves. The EPG interfaces directly with the engine's Engine Control Module (ECM) and a solid-state pressure transducer mounted on the pump discharge manifold.

+-------------------+        +--------------------+        +---------------------+
| Discharge Pressure| ------>| Electronic Pressure| ------>| Engine Control      |
| Transducer        | Signal | Governor (EPG)     | Signal | Module (ECM)        |
+-------------------+        +--------------------+        +---------------------+
                                                                      |
                                                                      v
                                                           Adjusts Fuel Injection Rate
                                                           (Engine RPM ↑ or ↓)

EPG Operating Modes: Pressure Mode vs. RPM Mode

Electronic governors feature two distinct operating modes selected by the driver/operator based on tactical priorities:

Operating ModePrimary Control ParameterSystem Response to Line ShutdownPrimary Fireground Application
Pressure ModeConstant Discharge Pressure (psi)Automatically throttles down engine RPM to maintain constant pressure on remaining attack lines.Handline attack operations, interior structural firefighting, multi-line operations.
RPM ModeConstant Engine Speed (RPM)Maintains fixed RPM; discharge pressure spikes on remaining lines when a hose line is shut down.Drafting operations, supply pumper in relay operations, high-capacity master streams.

Pressure Mode Operation

In Pressure Mode, the operator dials in a desired discharge pressure (e.g., 150 psi). The pressure transducer continuously samples manifold pressure hundreds of times per second. If a 1.75-inch handline is shut off, the transducer detects an instantaneous pressure rise to 170 psi and signals the EPG. The governor immediately instructs the engine ECM to reduce fuel injection, dropping engine RPM until discharge pressure returns precisely to 150 psi. Conversely, if a second attack line is opened, the EPG increases engine RPM to maintain 150 psi.

RPM Mode Operation

In RPM Mode, the EPG acts as a standard engine cruise control, holding engine speed at a fixed RPM (e.g., 1,800 RPM) regardless of water pressure fluctuations. RPM Mode is critical during drafting operations: if air momentarily enters the suction hose, pump pressure drops precipitously. In Pressure Mode, a governor would dangerously rev the engine to maximum RPM trying to restore pressure, accelerating cavitation. In RPM Mode, engine speed remains steady while the operator purges air.


Water Hammer Prevention & Line Shutdown Protocols

Water hammer is a severe hydraulic shock wave created when the velocity of water moving through a pipe or hose is suddenly stopped or redirected.

The Physics of Water Hammer

When a nozzle or valve is closed rapidly, the kinetic energy of the moving fluid column is converted instantaneously into potential pressure energy. The resulting pressure wave travels back through the hose line toward the pump at speeds up to 4,000 feet per second (1,200 m/s). Pressure spikes during water hammer can exceed 3 to 5 times normal operating pressure, causing:

  • Catastrophic hose ruptures and coupling detachment.
  • Shattered pump casings, internal valve gates, and piping joints.
  • Severe physical injury or loss of balance for firefighters holding handlines.

Mechanical Prevention Standards

To mitigate water hammer, NFPA 1901 requires that all discharge valves 3 inches (75 mm) or larger must be equipped with slow-operating valve actuators. These mechanical gear drives or electronic actuators require a minimum of 3 seconds to move from fully open to fully closed (or vice versa), ensuring water velocity drops gradually rather than instantaneously.

Driver/Operator Response to Line Shutdowns

When operating on the fireground, driver/operators must actively monitor panel gauges during line shutdowns:

  1. Observe the EPG status display to verify engine RPM throttles down smoothly in Pressure Mode.
  2. If operating mechanical relief valves, ensure the "Relief Valve Open" indicator light illuminates when lines are closed.
  3. If pressure spikes persist despite automated controls, manually gate down remaining discharges or adjust throttle controls to protect working crews.
Test Your Knowledge

Under NFPA 1901, an automatic pressure control device must prevent pump discharge pressure from exceeding the set pressure by more than how many psi during rapid line shutdowns?

A
B
C
D
Test Your Knowledge

During an interior structural attack with multiple handlines, which governor mode should the driver/operator select on an Electronic Pressure Governor (EPG)?

A
B
C
D
Test Your Knowledge

Why does NFPA 1901 require discharge valves 3 inches (75 mm) or larger to feature slow-operating mechanisms taking at least 3 seconds to open or close?

A
B
C
D