3.2 Raised Floor, Ceilings, Lighting, EPS & EMF
Key Takeaways
The raised access floor forms a pressurised supply-air plenum; perforated tiles or grates sit in the cold aisle, and brush grommets around cable cut-outs cut bypass air that wastes cooling and PUE.
Lighting has separate horizontal and vertical criteria; BICSI 002-2014 gives 500/200 lux measured 1 m above floor for occupied aisles.
Emergency-lighting levels and duration follow the adopted local code; do not equate EN escape-route criteria with NFPA average values.
Magnetic-field EMF is mitigated with high-permeability shielding (mu-metal, silicon steel); electric fields need conductive Faraday enclosures and RF needs ferrite/shielded cabling.
Signal-reference bonding can complement the code-required protective bonding network; use the designed connections for metallic supports and equipment.
The Raised Access Floor
The raised access floor (also called a raised floor or access floor) is a modular deck of removable tiles supported on pedestals and, in stiffer systems, connected by stringers, sitting above the structural slab. It serves two roles at once: it forms a pressurised plenum that distributes cooled supply air, and it provides a concealed space for power and data cabling. Typical plenum heights range from about 600 mm to 900 mm, and high-density or heavily cabled halls may go to 1200 mm to keep airflow unobstructed.
Loading and Airflow
Cabinet feet and wheels impose concentrated and rolling loads. Verify the complete floor and transport route against those loads, plus distributed loading; do not substitute a universal kg/m2 value. Cooled air is pushed into the plenum by CRAC/CRAH units and rises through perforated tiles or floor grates positioned in the cold aisle. Correct tile placement and plenum pressure are critical: too many open tiles in the wrong place starve distant racks and create hot spots, so many operators validate airflow with CFD (computational fluid dynamics) modelling.
Air that leaks out of the plenum anywhere except the cold-aisle tiles is wasted bypass air. Brush grommets seal around cables passing through floor cut-outs, and blanking panels close unused rack U-spaces — both are low-cost, high-impact ways to protect plenum pressure and lower PUE. Note that brush grommets are airflow-management devices, not fire-rated barriers.
Common trap — zinc whiskers: Older electroplated floor tiles can grow conductive zinc whiskers on their underside. Disturbed during work, these can enter the airstream and cause short circuits. It is a raised-floor-specific hazard that pure slab designs avoid, which is one reason some modern halls use overhead cabling on a slab floor.
Raised Floor vs Slab
The raised floor is not the only option. On a slab (no access floor) design, power and data run in overhead cable trays and cooling is delivered by overhead ducting or in-row/rear-door units instead of an under-floor plenum. A slab may remove access-floor load constraints, but its structural capacity must still be verified and removes the zinc-whisker and plenum-leakage problems, but it gives up the flexible under-floor air distribution that made raised floors the classic choice. The exam contrasts them as under vs over: raised floor distributes air and cable beneath the room within a load-limited plenum, while slab keeps everything overhead with no floor plenum. The fire design must assess concealed spaces and airflow. Aspirating sampling in a floor void is one option; the required coverage and detector technology depend on the adopted code and approved design.
Suspended Ceilings
A suspended (dropped) ceiling hung on a T-bar grid below the structural slab creates an overhead return-air plenum, houses lighting and cable trays, and conceals fire-suppression piping and detection. In hot-aisle containment designs the ceiling plenum often becomes the hot return path back to the CRAH units, so its integrity directly affects cooling efficiency.
Data Centre Lighting
Lighting is a balance between operational visibility and heat: every watt of light becomes heat the cooling plant must reject. An established ANSI/BICSI 002-2014 occupied-aisle recommendation is 500 lux horizontal and 200 lux vertical, measured 1 m above the finished floor. Use the applicable current project standard and local requirements; horizontal and vertical measurements are different. Excessive levels such as 1500 lux add needless heat, while too little light creates safety and ergonomic problems. Motion-activated LED fixtures reduce general lighting when unoccupied while preserving required security and egress illumination, cutting both energy and heat load.
Emergency Lighting and EPS
Safety of egress does not depend on the utility. Emergency lighting is backed by an Emergency Power Supply (EPS) — a central battery system, a standby generator, or self-contained battery luminaires. Emergency-lighting levels, uniformity, duration and transfer time are jurisdiction-specific. Do not treat a European escape-route minimum as an NFPA average: adopted NFPA requirements use different initial average and minimum values. Confirm the applicable code and provide immediate safe egress during source transitions.
EMF Sources and Shielding
Electromagnetic fields (EMF) in a data centre come from large transformers, motors, bus duct, UPS, and nearby high-voltage lines or rail systems. Strong fields can disrupt equipment or corrupt magnetic media, and shielding must be matched to the field type:
| Field type | Behaviour | Shielding approach |
|---|---|---|
| Magnetic (low-frequency) | Penetrates ordinary conductors easily | High-permeability mu-metal, silicon steel, or thick steel to redirect flux |
| Electric field | Blocked by conductors | Conductive enclosure / Faraday cage |
| Radio frequency (RF) | Couples onto cables | Ferrite chokes, shielded and filtered cabling |
Magnetic-field mitigation is the classic exam point: because magnetic flux slips through non-ferromagnetic barriers, you use high-permeability materials to divert it, not a simple metal box. EMF reduction may be required to meet ICNIRP human-exposure limits and equipment-immunity specifications, and the cheapest fix is often to locate the white space away from the source in the first place.
Signal Reference Grid, Bonding and Earthing
Two related concepts underpin electrical safety and signal integrity. Bonding ties metallic parts together to a common potential; protective bonding provides an effective fault-current return path to the source so protection can operate. Earthing establishes the system reference; soil alone is not a substitute for a fault-clearing conductor. Together they protect personnel, equipment, and data. Inside the white space the best practice is a Signal Reference Grid (SRG): a mesh of copper conductors integrated with the designed bonding network for metallic floor supports, racks and cabinets. This equipotential plane minimises common-mode noise and equalises ground-voltage differences during transients and lightning. EN 50310 (bonding and earthing for buildings with ICT) and IEEE 1100 (the Emerald Book) detail these designs. Remember the SRG complements the life-safety electrical bonding network — it does not replace the code-mandated protective earth.
In the cited BICSI 002-2014 occupied-aisle recommendation, how are the 500/200 lux levels measured?
Both values are horizontal measurements at floor level
500 lux horizontal and 200 lux vertical, 1 m above floor
500 lux vertical and 200 lux horizontal, at floor level
Both values are measured on the ceiling grid
Which shielding approach is appropriate for a strong LOW-FREQUENCY MAGNETIC field from a large transformer or bus duct near the white space?
A simple aluminium Faraday enclosure
Ferrite chokes clamped onto data cables
Better ventilation to disperse the field
High-permeability shielding such as mu-metal or silicon steel to redirect the flux
How should bonding of exposed metallic floor supports and equipment be specified?
Follow the designed protective bonding and signal-reference system
Use one arbitrary connection per five pedestals
Rely on slab contact as the protective conductor
Remove protective connections whenever noise is reported
Sections you finish are checked off in the contents.