8.3 Carbon Monoxide Thresholds, Safety Protocols, and Orphaned Water Heaters
Key Takeaways
- Carbon monoxide (CO) has a 200 to 250 times greater binding affinity for human hemoglobin than oxygen, forming carboxyhemoglobin (COHb), shifting the oxygen dissociation curve left, and starving vital tissues of oxygen.
- ANSI/BPI-1200-S-2017 sets indoor ambient CO action levels: below 9 ppm is normal background; 9-35 ppm requires notifying the occupant, opening windows, and checking sources; 36-69 ppm adds shutting off suspect appliances; and 70 ppm or greater requires terminating the inspection, evacuating the building, and notifying emergency services from outside.
- Flue gas carbon monoxide must be measured at steady-state operation and converted to Air-Free parts-per-million (ppm_AF) using oxygen readings: CO_air_free = CO_measured * (20.9 / (20.9 - %O2)) to prevent excess or dilution air from distorting the measurement.
- ANSI/BPI-1200-S-2017 Table 1 sets flue gas CO thresholds by appliance: 400 ppm air free for central furnaces, boilers, and clothes dryers; 200 ppm air free for water heaters, vented and unvented room heaters, and BIV wall furnaces; 225 ppm as measured for ovens and broilers; and 25 ppm as measured for gas-log fireplaces.
- The Orphaned Water Heater hazard occurs when an atmospheric furnace is decoupled from a shared masonry chimney and replaced with a sidewall-vented Category IV unit, leaving the small water heater alone in an oversized, cold chimney where buoyant draft collapses, spilling CO and condensing acidic moisture that destroys chimney mortar.
8.3 Carbon Monoxide Thresholds, Safety Protocols, and Orphaned Water Heaters
Quick Answer: Carbon monoxide ($CO$) is a lethal, odorless, and colorless byproduct of incomplete combustion that binds to human hemoglobin over 200 times more readily than oxygen, forming carboxyhemoglobin ($COHb$) and causing systemic hypoxia. Under ANSI/BPI-1200, ambient indoor air dictates immediate safety action: below 9 ppm is normal background; 9–35 ppm requires homeowner notification, opening windows and doors, and checking possible sources; 36–69 ppm adds a recommendation to shut off suspect appliances immediately; and 70 ppm or greater mandates terminating the inspection, evacuating the building, and notifying emergency services from outside. Any occupant showing CO-poisoning symptoms is an immediate evacuation trigger at any concentration. Flue gas $CO$ is evaluated on an air-free basis ($ppm_{AF}$) to eliminate dilution distortion, capped by ANSI/BPI-1200-S-2017 Table 1 at 200 ppm air free for water heaters, vented room heaters, and back-in-vent (BIV) wall furnaces, and 400 ppm air free for central furnaces, boilers, and direct-vent wall furnaces. A critical weatherization hazard is the orphaned water heater, which occurs when a furnace is decoupled from a shared masonry chimney, leaving a low-BTU water heater alone in a cold, oversized flue where buoyant draft fails, causing continuous spillage and acidic condensation that destroys chimney mortar.
Carbon Monoxide Physiology, Toxicology, and Pathology
Carbon monoxide ($CO$) is an invisible, odorless, tasteless, and non-irritating toxic gas with a molecular weight of 28.01 g/mol. This makes it virtually identical in density to ambient air (average molecular weight of 28.97 g/mol; specific gravity of 0.967). Because it does not rise to the ceiling like methane or settle to the floor like propane, carbon monoxide diffuses evenly throughout conditioned living spaces.
[ INHALED AIR WITH CO ]
|
v
Alveolar Capillary Beds
|
v
+-------------------------------------------------------------+
| BLOODSTREAM INTERACTION |
| |
| Oxygen (O2) + Hemoglobin <=====> Oxyhemoglobin |
| |
| Carbon Monoxide (CO) has 200x - 250x GREATER AFFINITY |
| |
| CO + Hemoglobin =====> Carboxyhemoglobin (COHb)|
| |
| * Locks hemoglobin binding sites |
| * Shifts oxygen dissociation curve left (Haldane effect) |
| * Prevents remaining O2 from releasing into tissues |
+-------------------------------------------------------------+
|
v
[ SYSTEMIC CELLULAR HYPOXIA ]
Brain, Heart, Vital Organs Starved of O2
Mechanism of Toxicity: Carboxyhemoglobin (COHb)
When inhaled, $CO$ diffuses across pulmonary alveolar membranes into the bloodstream, where it binds competitively to the iron atoms within hemoglobin tetramers. Hemoglobin's binding affinity for $CO$ is 200 to 250 times greater than its affinity for oxygen ($O_2$). Consequently, even minute concentrations of $CO$ in ambient air rapidly displace oxygen, transforming functional hemoglobin into carboxyhemoglobin ($COHb$).
Furthermore, $CO$ poisoning inflicts a double biological blow through the Haldane effect:
- When $CO$ binds to one of the four oxygen-binding heme sites on a hemoglobin molecule, it alters the three-dimensional protein conformation, shifting the oxygen-hemoglobin dissociation curve sharply to the left.
- This structural locking increases the binding affinity of the remaining three heme sites for oxygen, preventing oxyhemoglobin from releasing its bound oxygen into oxygen-starved peripheral tissues, particularly the brain and myocardium.
- Simultaneously, dissolved $CO$ in blood plasma diffuses into cells, binding to intracellular myoglobin and inhibiting cytochrome c oxidase in mitochondrial electron transport chains, shutting down cellular adenosine triphosphate (ATP) production and causing cellular necrosis.
Clinical Symptoms by Concentration and Exposure Duration
Because carbon monoxide poisoning mimics common viral illnesses, it is frequently misdiagnosed as the seasonal flu, food poisoning, or chronic fatigue syndrome.
| Ambient CO Concentration | Exposure Duration | Typical Physiological Symptoms | Blood COHb Level |
|---|---|---|---|
| 9 ppm | 24 Hours | EPA National Ambient Air Quality Standard ceiling; no acute symptoms | < 2% |
| 35 ppm | 8 Hours | OSHA allowable workplace limit; mild frontal headache after 6–8 hours | 2% – 5% |
| 50 – 100 ppm | 1 – 2 Hours | Moderate frontal headache, fatigue, nausea, flu-like symptoms, dizziness | 10% – 20% |
| 100 – 200 ppm | 1 Hour | Throbbing headache, confusion, weakness, impaired motor coordination | 20% – 30% |
| 400 ppm | 1 – 2 Hours | Severe headache, vomiting, disorientation, cognitive collapse | 30% – 40% |
| 800 ppm | 45 Minutes | Severe dizziness, nausea, convulsions, syncope, unconsciousness | 40% – 50% |
| 1,600+ ppm | < 20 Minutes | Coma, permanent neurological damage, cardiac arrest, rapid death | > 60% |
ANSI/BPI-1200 Ambient Air Carbon Monoxide Action Protocols
Energy auditors and weatherization professionals operate under strict ethical and procedural mandates regarding indoor carbon monoxide. Under ANSI/BPI-1200, the auditor must continuously monitor ambient indoor air from the moment they step onto the property.
+-------------------------------------------------------------------------+
| ANSI/BPI-1200 AMBIENT CO ACTION LEVELS |
+-------------------------------------------------------------------------+
| 0 to 9 ppm: NORMAL / ACCEPTABLE |
| * Normal indoor background level. Proceed with audit. |
+-------------------------------------------------------------------------+
|
v
+-------------------------------------------------------------------------+
| 9 to 35 ppm: WARNING LEVEL |
| * Inform homeowner/occupants of elevated reading. |
| * Investigate potential sources (stove, water heater, attached garage).|
| * Advise servicing; audit may proceed with caution. |
+-------------------------------------------------------------------------+
|
v
+-------------------------------------------------------------------------+
| 36 to 69 ppm: ELEVATED HAZARD |
| * IMMEDIATELY TURN OFF suspect combustion appliances. |
| * Open windows and doors to ventilate the home. |
| * Inform occupants and recommend certified HVAC service. |
| * DO NOT proceed with combustion testing until levels drop < 35 ppm. |
+-------------------------------------------------------------------------+
|
v
+-------------------------------------------------------------------------+
| 70+ ppm (or ANY level with occupant symptoms): IMMEDIATE EMERGENCY |
| * EVACUATE ALL OCCUPANTS AND YOURSELF IMMEDIATELY. |
| * DO NOT pause to collect tools. Leave doors open behind you. |
| * CALL 911 / EMERGENCY SERVICES from outside the structure. |
| * Do NOT re-enter under any circumstances. |
+-------------------------------------------------------------------------+
Detailed Breakdown of Ambient Action Levels
- 0 to 9 ppm (Normal Background): Represents safe, standard indoor air quality. The energy auditor may proceed with all standard diagnostic testing, including blower door depressurization.
- 9 to 35 ppm (Investigation Level): Ambient levels are elevated above outdoor baseline. The auditor must inform the homeowner, locate the source of emission (such as an unvented space heater, idling vehicle in an attached garage, or gas cooktop), advise the client to seek mechanical inspection, and proceed with caution.
- 36 to 69 ppm (Elevated Hazard Level): Serious combustion malfunction. The auditor must immediately turn off suspect combustion appliances, open exterior windows and doors to ventilate the living area, inform the occupants, and advise that the equipment must be inspected and serviced by a certified HVAC technician. Diagnostics must cease until indoor ambient CO drops below 35 ppm.
- >= 70 ppm — Immediate Emergency Evacuation: Section 7.3.3.3.1 of ANSI/BPI-1200-S-2017 requires the auditor to terminate the inspection at 70 ppm or greater. Standard field safety practice extends the same response to any concentration at which an occupant or technician exhibits symptoms of CO poisoning (headache, nausea, dizziness). In either case the auditor must order an IMMEDIATE EVACUATION of all occupants. Leave exterior doors open during exit to ventilate, retreat to a safe outdoor location, and call 911 / emergency first responders. Under no circumstances should anyone re-enter the structure until emergency services have cleared the building with calibrated gas detection instruments.
Operational Rules for Field Monitoring
- Outdoor Calibration / Zeroing: The carbon monoxide monitor must be powered on and zeroed in fresh, clean outdoor air prior to crossing the building threshold.
- Breathing-Zone Monitoring: The detector must be worn on the auditor's outer clothing at breathing-zone height (chest or lapel) throughout the audit.
- Pre-Blower Door Screen: The auditor must measure ambient CO throughout the living space and CAZ before running a blower door. Depressurizing a home with high baseline CO can violently backdraft flues and poison occupants.
Flue Gas Carbon Monoxide and the Air-Free Calculation
When evaluating combustion safety inside an appliance vent connector pipe, measuring raw parts-per-million ($ppm$) of $CO$ is scientifically invalid because excess air and dilution air dilute the concentration.
Why Raw Flue Readings Are Scientifically Misleading
Consider two identical gas furnaces producing the exact same physical mass of carbon monoxide molecules per minute:
- Furnace A operates with minimal excess air (20%). A combustion analyzer inserted into the flue measures 120 ppm raw $CO$.
- Furnace B operates with a loose draft hood that entrains massive quantities of dilution air (150% excess air). The analyzer measures only 45 ppm raw $CO$.
Although Furnace B displays a much lower raw reading on the screen, both burners are producing identical quantities of poison. The reading in Furnace B is artificially suppressed because dilution air entered the exhaust stream. To eliminate this confounding dilution variable, building science converts measured raw $CO$ into Air-Free Carbon Monoxide ($ppm_{AF}$)—the theoretical concentration of $CO$ that would exist in completely undiluted, oxygen-free combustion exhaust.
The Mathematical Air-Free Derivation and Formula
Using the volumetric percentage of oxygen ($%O_2$) measured in the flue gas, air-free $CO$ is calculated as:
Where:
- $CO_{\text{air-free}}$ is the normalized, undiluted carbon monoxide concentration in parts-per-million ($ppm_{AF}$).
- $CO_{\text{measured}}$ is the raw, unadjusted $CO$ reading displayed by the combustion analyzer ($ppm$).
- $20.9$ is the volumetric percentage of oxygen in dry atmospheric air.
- $%O_2$ is the percentage of oxygen remaining in the flue gas stream.
(Note: If the analyzer measures carbon dioxide ($%CO_2$) instead of oxygen, the alternative formula is: $CO_{\text{air-free}} = CO_{\text{measured}} \times \left[ \frac{CO_{2,\text{ultimate}}}{CO_{2,\text{measured}}} \right]$, where $CO_{2,\text{ultimate}}$ for natural gas is approximately 11.9% to 12.2%.)
Mathematical Step-by-Step Calculation Example
An energy auditor tests a natural gas central heating furnace operating at steady state:
- Measured raw $CO$: 95 ppm
- Measured flue oxygen ($%O_2$): 8.2%
Calculation:
Notice that dilution air made the burner appear cleaner (95 ppm) than it actually was ($156\text{ ppm}_{AF}$). The air-free value reveals the true combustion quality.
BPI Appliance Flue Gas CO Action Thresholds
Under ANSI/BPI-1200-S-2017, undiluted flue gas $CO$ is measured at 5 minutes of main burner operation and compared against the per-appliance thresholds in the standard's Table 1. Note that most limits are stated air free, but ovens, broilers, gas refrigerators, and gas-log fireplaces are judged as measured:
| Appliance Classification (Table 1) | Threshold Limit | Required Diagnostic Action if Limit Exceeded |
|---|---|---|
| Central Furnace (all categories) | 400 ppm air free | Service required; inspect for cracked heat exchanger, check manifold gas pressure |
| Boiler | 400 ppm air free | Service required; clean boiler heat exchanger sections and burner tubes |
| Floor Furnace / Gravity Furnace | 400 ppm air free | Service required; inspect burners, heat exchanger, and vent connector |
| Wall Furnace (BIV — back-in-vent) | 200 ppm air free | Service required; verify heat exchanger integrity and combustion air supply |
| Wall Furnace (Direct Vent) | 400 ppm air free | Service required; verify sealed intake and exhaust terminations are unobstructed |
| Vented Room Heater | 200 ppm air free | Service required; verify vent connector rise, pitch, and combustion air supply |
| Unvented Room Heater | 200 ppm air free | Advise homeowner; verify room volume and combustion air compliance |
| Domestic Water Heater | 200 ppm air free | Service required; investigate gas pressure, draft, and burner orifice cleanliness |
| Oven / Broiler | 225 ppm as measured | Service required; clean burner ports; test ambient kitchen CO during bake cycle |
| Clothes Dryer | 400 ppm air free | Service required; clear lint blockage and verify exhaust termination |
| Refrigerator (gas absorption) | 25 ppm as measured | Service required; inspect burner and vent |
| Gas Log (gas fireplace) | 25 ppm as measured in vent | Service required; inspect burner, logs placement, and venting |
| Gas Log (installed in wood-burning fireplace) | 400 ppm air free in firebox | Service required; verify damper position and log set installation |
Core BPI Exam Thresholds: Memorize these benchmarks cold: 400 ppm air free for central furnaces, boilers, and clothes dryers; 200 ppm air free for domestic water heaters, vented and unvented room heaters, and BIV wall furnaces; 225 ppm as measured for ovens and broilers; 25 ppm as measured for gas-log fireplaces and gas refrigerators. Note the distinction the standard makes between air free limits (calculated from the oxygen reading) and as measured limits (read directly off the analyzer).
The Orphaned Water Heater Phenomenon
The "orphaned water heater" is one of the most widespread, dangerous safety failures created during residential energy efficiency upgrades.
+-------------------------------------------------------------------------+
| BEFORE RETROFIT: COMMON CHIMNEY |
+-------------------------------------------------------------------------+
| |
| Shared Masonry Chimney |
| (8" x 12" Clay Tile Liner) |
| ^ |
| | 136,000 BTU/hr Total Heat |
| | High Flue Velocity & Hot Flue Gases |
| +----------+----------+ |
| | | |
| +-------+-------+ +-------+-------+ |
| | Furnace Flue | |Water Htr Flue | |
| | 100,000 BTU/hr| | 36,000 BTU/hr | |
| +---------------+ +---------------+ |
| (High Heat Keeps Chimney Warm ===> Strong Natural Draft) |
+-------------------------------------------------------------------------+
|
v [ Energy Upgrade: Install 96% AFUE Furnace ]
+-------------------------------------------------------------------------+
| AFTER RETROFIT: THE ORPHANED HAZARD |
+-------------------------------------------------------------------------+
| |
| New 96% Furnace Oversized, Freezing Masonry Chimney |
| Vents Out Sidewall (Cold Brick Chills Small Flue Stream) |
| with 2" PVC |
| =====> (Sidewall) | |
| v |
| +--------+--------+ |
| | Water Htr Flue | |
| | 36,000 BTU/hr | |
| +-----------------+ |
| * Flue gases cool < 130°F |
| * Buoyant draft FAILS |
| * Acidic moisture dissolves |
| chimney lime mortar |
| * CONTINUOUS SPILLAGE & CO |
+-------------------------------------------------------------------------+
1. The Architectural Setup
In millions of homes built between 1940 and 1990, an atmospheric furnace (80,000 to 120,000 BTU/hr) and a standard atmospheric water heater (34,000 to 40,000 BTU/hr) shared a common brick masonry chimney lined with 8"x8" or 8"x12" clay flue tiles (having an internal cross-sectional area of 64 to 96 square inches):
- Together, their combined firing rate of 114,000 to 160,000 BTU/hr injected massive quantities of thermal energy into the chimney.
- High exhaust velocities and high flue temperatures (400°F to 500°F) easily overcame the thermal mass of the cold brickwork, establishing a powerful, reliable upward stack draft.
2. The Energy Retrofit Upgrade
The homeowner upgrades their old heating system by installing a modern, high-efficiency Category IV 96% AFUE condensing gas furnace. The new condensing furnace vents directly through the basement rim joist and exterior sidewall using 2-inch or 3-inch plastic PVC pipe. The contractor caps off the old furnace flue connection at the chimney breast, leaving the original 34,000 BTU/hr natural-draft water heater connected alone to the existing masonry chimney.
3. The Physical Failure Cascade
The water heater is now "orphaned" in a masonry chimney that is massively oversized for its small firing rate:
- Oversized Flue Geometry: Under NFPA 54 vent sizing tables, a 34,000 BTU/hr water heater requires a 3-inch or 4-inch vent pipe (having an area of only 7 to 12.5 square inches). The 8"x12" masonry chimney is 6 to 8 times larger than the appliance requires!
- Thermal Buoyancy Collapse: The tiny burner cannot generate enough heat or exhaust volume to warm the tons of cold brick and clay masonry. As flue gases enter the massive chimney, their upward velocity plunges ($v = Q / A$). Flue gases stall, cool rapidly, and lose all buoyant stack pressure.
- Chronic Flue Gas Spillage: Because the chimney fails to establish draft, combustion byproducts back up and spill continuously out of the water heater draft hood directly into the basement, contaminating the home with carbon monoxide and combustion moisture.
- Acidic Condensation & Chimney Destruction: As stalled flue gases cool below their dew point (approximately 130°F), gallons of water vapor condense into liquid acid inside the flue. The acidic condensate dissolves the alkaline calcium carbonate in the lime mortar between the chimney bricks and clay tiles. Over several seasons:
- Mortar joints dissolve and crumble into sand.
- Clay flue tiles spall, crack, and collapse into the bottom of the chimney.
- Fallen debris completely blocks the water heater flue collar, resulting in 100% of combustion gases dumping directly into the home.
4. Walkthrough Diagnostic Indicators of an Orphaned Water Heater
During an energy audit, analysts identify orphaned water heaters by looking for classic physical symptoms:
- Melted Plastic Grommets: The plastic trim rings (cold inlet and hot outlet grommets) on top of the water heater casing are warped, curled, or melted. Building Science Rule: Melted grommets are definitive physical proof of repeated, severe flue gas spillage at the draft hood.
- Corrosion and Rust: Heavy rust and flaking metal around the draft hood collar, vent connector screws, and the top outer jacket of the tank.
- White Efflorescence: White, powdery mineral salt deposits leaching through exterior brick mortar joints on the chimney exterior, indicating acidic moisture penetrating the brickwork.
- Sooting: Carbon soot deposits staining the draft diverter, water heater tank jacket, or overhead floor joists.
+-------------------------------------------------------------------------+
| DIAGNOSTIC SIGNS OF AN ORPHANED HEATER |
+-------------------------------------------------------------------------+
| [1] Melted plastic pipe grommets on top of water heater casing |
| [2] Heavy rust and acid corrosion around draft hood collar |
| [3] White efflorescence leaching through exterior brick mortar joints |
| [4] Chimney base full of collapsed clay tile and dissolved mortar sand |
+-------------------------------------------------------------------------+
5. Code-Compliant Remediation Measures
When an orphaned water heater is discovered, weatherization air sealing cannot proceed until the venting hazard is remediated using one of three approved strategies:
- Install an Approved Metal Chimney Liner: Drop an engineered, correctly sized flexible or rigid Type B aluminum or stainless steel chimney liner down the masonry chimney (typically 3-inch or 4-inch diameter for a standard 36,000 BTU water heater). The small liner restricts the cross-sectional area to match the water heater's input, allowing the appliance to quickly warm the liner and maintain reliable thermal draft.
- Upgrade to a Power-Vented or Direct-Vent Water Heater: Replace the atmospheric water heater with a Category III or IV unit that mechanically forces flue gases out through a sidewall pipe, abandoning the masonry chimney entirely.
- Electrify with a Heat Pump Water Heater (HPWH): Replace the fossil-fuel appliance with an ultra-efficient electric Heat Pump Water Heater (ENERGY STAR certified, UEF > 3.5). This permanently eliminates the combustion safety hazard from the CAZ, removes all chimney venting requirements, and provides free basement dehumidification.
Concrete Residential Case Study: Test-Out Catastrophe Averted
During a post-retrofit quality assurance audit in upstate New York, a BPI technician inspects a home that just received attic air sealing, dense-pack wall insulation, and a new 96% AFUE condensing gas furnace vented through the basement foundation rim joist.
Walkthrough Observation: The original 1998 40-gallon atmospheric gas water heater (36,000 BTU/hr) was left connected to the original 8"x12" exterior brick masonry chimney. The plastic cold-water inlet trim ring is warped and melted.
Diagnostic Testing:
- Ambient CO in basement: 4 ppm (normal background).
- Technician fires the water heater under natural baseline conditions (exhaust fans OFF).
- Smoke pen test at draft hood: At 30 seconds, smoke spills heavily into the basement. At 60 seconds, spillage continues. At 3 minutes, 100% of flue gas is spilling across the basement floor. Flue draft probe on Channel B reads 0.00 Pa.
- Combustion analyzer inserted into the water heater draft diverter measures 165 ppm raw CO at 9.2% $O_2$:
Action Taken: The water heater failed both the spillage assessment at 2 minutes of main burner operation and the 200 ppm air free flue gas threshold for water heaters ($295\text{ ppm}{AF} > 200\text{ ppm}{AF}$). The technician immediately shuts off the gas supply valve to the water heater, applies an official warning red-tag, notifies the homeowner in writing, and coordinates the emergency installation of a 4-inch aluminum chimney liner and a complete burner tune-up before sign-off.
BPI Exam Tips & Common Traps
- The Evacuation Trigger Trap: On the exam, remember the exact dividing line between shutting down equipment vs. complete building evacuation:
- 9 to 35 ppm: Inform the client, open windows and doors, recommend that possible CO sources be checked.
- 36 to 69 ppm: All of the above, plus recommend that all possible sources be turned off immediately and that a qualified professional be contacted.
- >= 70 ppm: IMMEDIATE BUILDING EVACUATION of all occupants and termination of the inspection; notify emergency services from outside. Symptomatic occupants trigger the same response at any reading.
- The Orphaned Water Heater Definition: Expect exam questions describing a furnace replacement that leaves an atmospheric water heater alone in an existing masonry chimney. The correct answer focuses on insufficient draft due to an oversized flue, continuous spillage, and acidic condensation destroying chimney mortar.
- Melted Grommets as an Indicator: If an exam question mentions melted plastic water pipe grommets on top of a water heater, this is the classic visual hallmark of draft hood flue gas spillage and backdrafting.
- Air-Free Math Shortcut: Understand the formula dynamics: because ambient air contains oxygen, the denominator $(20.9 - %O_2)$ is always smaller than 20.9, meaning the multiplier is always greater than 1.0. Therefore, air-free CO will ALWAYS be higher than measured raw CO!
An energy auditor conducting an initial building walkthrough records an ambient carbon monoxide (CO) reading of 48 ppm in the basement CAZ, and the homeowner reports experiencing a persistent frontal headache and mild nausea. According to ANSI/BPI-1200 safety action protocols, what action must the auditor immediately take?
A combustion efficiency analyzer inserted into the flue connector of an atmospheric gas water heater measures a raw CO concentration of 60 ppm with an oxygen (O2) reading of 8.9%. What is the calculated air-free carbon monoxide concentration (CO_air_free)?
During a residential energy retrofit, an old 80% AFUE furnace is replaced with a 96% AFUE condensing furnace vented through a sidewall PVC pipe. The existing atmospheric gas water heater is left connected alone to the original 8"x12" brick masonry chimney. What severe safety and building durability hazard does this create?