PracticeVideosBlogFlashcards

5.1 Supply & Return Air Distribution Hardware (Grilles, Registers, Diffusers)

Key Takeaways

  • Grilles, registers, and diffusers (GRD) serve distinct aerodynamic roles: grilles are decorative or protective louvered coverings without volume control; registers combine grilles with integral volume-control dampers (typically opposed blade dampers); diffusers incorporate engineered directional vanes to induce room air entrainment and distribute supply air along predictable multi-directional patterns.

  • Supply air jet performance is governed by throw (distance to terminal velocity, typically T_150, T_100, or T_50 at 50 FPM), spread (lateral expansion angle of the jet), and drop (vertical downward deflection of chilled supply air driven by negative thermal buoyancy and Archimedes forces).

  • The Coanda effect (surface effect) occurs when a supply jet discharged parallel to a ceiling creates a localized sub-atmospheric pressure zone between the jet and the ceiling boundary, causing the air to cling to the ceiling, extending throw by 20% to 30% and preventing cold air dumping into the occupied zone.

  • Noise Criteria (NC) ratings establish permissible terminal sound thresholds: private offices and bedrooms require NC 25–30, general classrooms and open offices require NC 30–35, and commercial retail spaces require NC 35–40; excessive grille face velocities (above 500–700 FPM for supply and 400–500 FPM for return) generate audible aerodynamic turbulence and whistling.

  • Return air grilles must be sized according to effective free area (A_k), maintaining face velocities below 400–500 FPM for non-filtered grilles and 200–300 FPM for filter-grilles to avoid excessive static pressure drop, dust blow-through, and acoustic rumble.

Last updated: September 2026

5.1 Supply & Return Air Distribution Hardware (Grilles, Registers, Diffusers)

Note

Core Function of Air Distribution: The primary objective of an HVAC air distribution system is to deliver conditioned air to the occupied zone of a building in a manner that maintains uniform thermal comfort, prevents draftiness or stagnant air stratification, and operates quietly within acceptable acoustic thresholds. Even the most precisely sized air handler or chiller will fail to satisfy building occupants if terminal grilles, registers, and diffusers (GRD) are selected or installed incorrectly.


Classifying Hardware: Grilles vs. Registers vs. Diffusers

Although trade vernacular frequently uses the terms interchangeably, grilles, registers, and diffusers represent three distinctly engineered mechanical terminal devices with specific fluid flow characteristics, pressure profiles, and operational applications.

Terminal DeviceDefining CharacteristicsIntegral DamperPrimary ApplicationsTypical Aerodynamic Behavior
GrillePerforated, louvered, or bar-faced screen without an integral volume-control damperNo (Non-dampered)Return air inlets, exhaust air pickups, transfer air grilles, and relief openingsLow-resistance air intake or transfer; does not discharge directional throw jets
RegisterGrille assembly equipped with an integral manual or motor-actuated volume control damperYes (Typically Opposed Blade Damper - OBD)Supply outlets in residential and light-commercial sidewall and floor locationsDelivers directional supply air while allowing local trimming of delivered volume (CFM)
DiffuserEngineered supply terminal featuring contoured vanes, concentric cones, or linear slotsOptional (Duct balancing damper preferred over neck damper)Ceiling supply outlets in commercial and residential central air systemsHigh room air induction (entrainment), multi-directional air pattern (360°, 4-way, 2-way, slot), horizontal ceiling attachment

Grilles

A grille consists of a frame holding fixed or adjustable deflection vanes, egg-crate louvers, or perforated metal mesh. Because grilles lack integral volume-control dampers, they cannot throttle or balance airflow at the terminal face. Grilles are primarily specified for return air and exhaust air openings, where quiet, low-velocity intake is required without creating unnecessary static pressure resistance. When grilles are used for supply distribution (such as residential high-sidewall supply grilles), balancing must be performed using an inline branch damper located in the upstream ductwork.

Registers

A register is a grille factory-fitted with an integral volume control damper. In residential applications, registers are standard for floor boots, toe-kicks, and sidewall supply terminations. The integral damper enables occupants or balancing technicians to adjust or shut off airflow at the terminal device. However, closing register dampers increases system external static pressure (ESP) and can generate audible air-rush noise if the system is not designed with variable-speed bypass or zone relief.

Damper Types: Opposed Blade vs. Parallel Blade

Two primary damper blade configurations are utilized in air distribution hardware:

  • Opposed Blade Dampers (OBD): Adjacent blades rotate in opposite directions (one clockwise, the adjacent blade counter-clockwise). This counter-rotation maintains a symmetrical, uniform velocity profile across the entire face of the terminal, preventing air from being deflected to one side of the grille. OBDs provide superior linear throttling and generate significantly less aerodynamic noise during airflow modulation, making them the industry standard for terminal registers and balancing collars.
  • Parallel Blade Dampers (PBD): All blades rotate in the same rotational direction. As the damper modulates toward a closed position, air is deflected toward one side of the duct or grille neck, causing asymmetrical jet discharge, localized high face velocities, and severe acoustic hiss. Parallel blade dampers are rarely permitted at terminal devices and are primarily reserved for two-position (open/closed) outdoor air intake and exhaust dampers.

Diffusers

A diffuser is an aerodynamically contoured terminal device engineered to discharge supply air in diverse directions (such as 4-way, 3-way, 2-way, or radial 360-degree patterns) along a surface boundary (typically the ceiling). Unlike simple grilles that blow a concentrated, high-velocity jet into the room, diffusers utilize divergent geometry to rapidly reduce discharge velocity, convert velocity pressure into room air induction, and establish uniform thermal mixing.

Induction Ratio (Entrainment Ratio)

The defining engineering advantage of a ceiling diffuser is its high induction ratio (also termed the entrainment ratio). As high-velocity primary supply air emerges through the diffuser vanes, it creates localized low-pressure shear zones along the edges of the jet. This pressure differential draws large volumes of ambient room air (secondary air) into the primary jet stream, mixing the two air masses immediately at the ceiling level:

Induction Ratio=Total Air Stream Volume (Primary + Induced Room Air)Primary Supply Air Volume\text{Induction Ratio} = \frac{\text{Total Air Stream Volume (Primary + Induced Room Air)}}{\text{Primary Supply Air Volume}}

High-performance ceiling diffusers achieve induction ratios between 10:1 and 20:1. This rapid mixing tempers cold supply air (e.g., 55∘F55^\circ\text{F}) with warm ambient room air (e.g., 75∘F75^\circ\text{F}) within inches of the discharge face, raising the temperature of the moving air stream before it enters the occupied zone and eliminating cold thermal drafts.


Fluid Dynamics of Air Jets: Throw, Spread, and Drop

Proper selection and placement of supply air outlets requires an exact understanding of supply jet behavior. When conditioned air leaves an outlet, its trajectory is governed by momentum, friction with ambient air, and thermal buoyancy.

Diffuser Discharge
      │
      ▼
  ┌───────┐==================== Ceiling Surface ====================
  │       │~~~~~~~~~~~~~ High-Velocity Primary Jet ~~~~~~~~~~~~~~
  └───────┘     ───►                      ───►                 ───►
     ▲              Entrained Room Air (Induction)       Terminal Velocity (Vt)
     │              ▲                         ▲          (e.g., 50 FPM at T_50)
   Supply           │                         │                   │
    Air             └─────────────────────────┘                   ▼
   (55°F)                                                  Drop Boundary
                                                                  │
────────────────── Occupied Zone Boundary (6 ft AFF) ─────────────┼────────
                                                                  ▼
                                                             Human Occupant

1. Throw

Throw (TT) is the physical distance traversed by a supply air jet from the outlet face to a point where the core velocity decays to a specified terminal velocity (VtV_t). Manufacturers publish throw values in engineering catalogs based on three standardized terminal velocities:

  • T150T_{150}: Distance from the outlet to where the air stream velocity drops to 150 FPM150\text{ FPM}. This represents the high-energy core jet.
  • T100T_{100}: Distance to where jet velocity slows to 100 FPM100\text{ FPM}. This point marks the transition zone where secondary room air induction is largely complete.
  • T50T_{50}: Distance to where jet velocity slows to 50 FPM50\text{ FPM}. This is the standard engineering threshold for the boundary of the occupied zone.

In standard comfort cooling design, human occupants perceive air movement above 50 FPM50\text{ FPM} at 55∘F55^\circ\text{F} to 65∘F65^\circ\text{F} as an objectionable cold draft. Therefore, diffusers must be spaced so that the T50T_{50} throw distance terminates before the jet reaches an opposite wall or collides with a converging jet from an adjacent diffuser.

2. Spread

Spread is the divergent lateral angle or total width of the air stream in the horizontal or vertical plane after leaving the outlet. A wide-spread diffuser spreads air across a broad fan shape (e.g., a 4-way ceiling diffuser spreading air across 360 degrees), while a pencil-jet or linear nozzle provides minimal spread, concentrating momentum over a long distance.

3. Drop

Drop is the vertical downward distance that the lower boundary of a horizontally discharged cool air jet falls below the outlet centerline as it travels toward its terminal velocity. Drop is governed by the Archimedes Number, which balances thermal buoyant forces against inertial momentum forces:

  • When cold supply air (55∘F55^\circ\text{F}, density ≈0.077 lb/ft3\approx 0.077\text{ lb/ft}^3) is discharged into a warmer room (75∘F75^\circ\text{F}, density ≈0.074 lb/ft3\approx 0.074\text{ lb/ft}^3), the cold air is heavier and more dense than the ambient air.
  • If the initial discharge velocity is too low, or if the jet lacks ceiling boundary support, gravitational forces overcome kinetic momentum, causing the dense cold air to plunge prematurely into the room—a failure condition known as dumping.

The Coanda Effect (Surface Attachment)

The Coanda effect (also referred to in mechanical engineering as surface effect or ceiling attachment) is the physical tendency of a moving fluid jet to stay attached to a contiguous flat surface.

Physical Mechanism of Ceiling Attachment

When a supply diffuser discharges air directly parallel to and flush with a flat ceiling:

  1. The expanding supply jet entrains room air from its lower exposed surface, drawing room air upward into the jet stream.
  2. On the upper side of the jet facing the ceiling, air entrainment is physically restricted because the solid ceiling prevents room air from replenishing the space between the jet and the ceiling surface.
  3. This restriction creates a localized sub-atmospheric low-pressure zone (partial vacuum) between the moving air stream and the ceiling plane.
  4. The higher ambient room pressure below the jet forces the airstream upward, holding the jet tightly against the ceiling surface.

Engineering Consequences of the Coanda Effect

  • Extended Throw: Attachment reduces turbulent friction on the upper boundary of the jet, increasing total throw distance by 20% to 30%20\%\text{ to }30\% compared to a free, unattached jet discharged into open space.
  • Minimized Drop: Because the jet is held against the ceiling by the Coanda pressure differential, downward thermal drop is delayed until the jet has substantially slowed and warmed through secondary air mixing.
  • Loss of Coanda Effect: If a ceiling diffuser is installed in an open architectural ceiling where it is suspended more than 12 inches below the ceiling plane, or if structural concrete beams, joists, or surface-mounted light troffers interrupt the ceiling boundary, the Coanda effect is completely destroyed. Without ceiling attachment, cold supply air immediately separates from the horizontal plane and drops straight down into the occupied space, producing severe thermal complaints.

Air Diffusion Performance Index (ADPI)

The Air Diffusion Performance Index (ADPI) is a standardized metric established by ASHRAE to quantify the overall thermal and velocity comfort delivered by an air distribution system within an occupied space. The occupied zone is formally defined as the volume bounded by:

  • Floor level up to 6 feet above the finished floor (AFF).
  • Walls inward by at least 1.0 foot (12 inches) from perimeter walls or windows.

Effective Draft Temperature (EDT)

ADPI is calculated by measuring the Effective Draft Temperature (EDT) across an array of uniformly distributed test sensors within the occupied zone:

θ=(Tx−Tc)−0.07×(Vx−30)\theta = (T_x - T_c) - 0.07 \times (V_x - 30)

Where:

  • θ\theta = Effective draft temperature (°F)
  • TxT_x = Local dry-bulb air temperature at the measurement point (°F)
  • TcT_c = Average room dry-bulb comfort temperature (°F)
  • VxV_x = Local air velocity at the measurement point (FPM)
  • 3030 = Baseline still-air velocity (FPM)

ADPI Rating Standards

A test point is classified as thermally comfortable if:

  1. The Effective Draft Temperature (θ\theta) falls between −3.0∘F-3.0^\circ\text{F} and +2.0∘F+2.0^\circ\text{F}.
  2. The local air velocity (VxV_x) remains less than 70 FPM70\text{ FPM} (with optimum comfort between 30 and 50 FPM30\text{ and }50\text{ FPM}).
ADPI=(Number of Measurement Points Meeting Comfort CriteriaTotal Number of Measurement Points)×100%\text{ADPI} = \left( \frac{\text{Number of Measurement Points Meeting Comfort Criteria}}{\text{Total Number of Measurement Points}} \right) \times 100\%

An air distribution system achieves an acceptable design rating when the ADPI is 80%80\% or higher. High-performance 4-way and circular ceiling diffusers operating within their design throw-to-room-length ratio (T50/LT_{50} / L) typically achieve ADPI ratings between 85%85\% and 95%95\%.


Acoustic Design Standards: Noise Criteria (NC Ratings)

Air distribution terminals are primary sources of indoor ambient noise. When pressurized air forces its way through damper blades, perforations, and directional vanes, it generates broadband aerodynamic turbulence. In engineering design, this acoustic energy is rated using Noise Criteria (NC) curves.

NC Curves and Sound Pressure

An NC curve is a single-number rating derived by plotting octave band sound pressure levels (measured in decibels, dB, across eight standard frequency bands from 63 Hz63\text{ Hz} to 8,000 Hz8,000\text{ Hz}) against standardized human acoustic sensitivity contours. Because the human ear is less sensitive to low-frequency rumble (63−125 Hz63-125\text{ Hz}) than to high-frequency speech-interference hiss (1,000−4,000 Hz1,000-4,000\text{ Hz}), NC curves allow higher decibel levels at lower frequencies.

Space ClassificationDesign NC RangeMaximum Outlet Face VelocityPrimary Acoustic Risk
Broadcast / Sound Recording StudiosNC 15 – 20250−350 FPM250 - 350\text{ FPM}Structural vibration, damper whistling, microphonic pickup
Executive Offices, Bedrooms, ChurchesNC 25 – 30400−500 FPM400 - 500\text{ FPM}Low-frequency duct rumble, register damper turbulence
General Open Offices, Classrooms, LibrariesNC 30 – 35500−650 FPM500 - 650\text{ FPM}Diffuser neck generation, high velocity through core
Commercial Retail, Dining, CafeteriasNC 35 – 40700−850 FPM700 - 850\text{ FPM}Return grille roar, unlined duct breakout noise
Industrial Warehouses, Mechanical RoomsNC 45 – 55+1,000−1,500 FPM1,000 - 1,500\text{ FPM}High static fan noise, broad-spectrum aerodynamic roar

Aerodynamic Noise Prevention

  1. Do Not Balance at the Diffuser Neck: Utilizing an opposed blade damper directly on the back of a ceiling diffuser neck to throttle high airflow creates intense localized turbulence and sharp high-frequency whistling directly at the room boundary. All primary system balancing must be performed using an inline volume damper located at least 5 to 10 duct diameters upstream in the rigid branch takeoff.
  2. Avoid Direct Line-of-Sight Sound Paths: Return air openings cut directly into gypsum board walls without acoustic duct boots allow compressor, blower, and damper noise to transmit straight into occupied spaces.
  3. Maintain Conservative Neck Velocities: Diffusers should generally be selected for neck velocities between 400 and 600 FPM400\text{ and }600\text{ FPM} in commercial office environments to maintain sound levels below NC 30.

Return Air and Filter-Grille Sizing (Free Area AkA_k)

While supply diffusers project concentrated, directional jets across long distances, return air grilles do not project directional streams. Air is drawn into a return grille from all directions (spherical velocity decay). At a distance of merely one duct diameter away from the face of a return grille, air velocity drops to less than 10%10\% of the face velocity.

Gross Area vs. Core Area vs. Effective Free Area (AkA_k)

When calculating airflow across a grille or register, contractors must never use the gross nominal frame dimensions:

  • Gross Area: Total outer dimensions including the mounting flange.
  • Core Area: The interior duct opening dimensions bounded by the inner frame.
  • Effective Free Area (AkA_k): The actual, unobstructed open area through which air passes, accounting for the physical blockage caused by louvers, blades, and frame borders. The ratio of free area to core area typically ranges from 60% to 75%60\%\text{ to }75\% for stamped steel grilles.

Airflow through any terminal device is governed by the AkA_k equation:

CFM=Ak×Vk\text{CFM} = A_k \times V_k

Where:

  • CFM\text{CFM} = Volumetric airflow rate (Cubic Feet per Minute)
  • AkA_k = Manufacturer-published effective free area (ft2\text{ft}^2)
  • VkV_k = Average face velocity measured at specified test points across the core (FPM)

Velocity Limits for Return and Filter Grilles

  • Non-Filtered Return Grilles: Recommended face velocity is 400 to 500 FPM400\text{ to }500\text{ FPM}. Higher velocities create audible air rushing, while lower velocities require excessively large architectural openings.
  • Filter-Grilles (Central Return Air Filter Racks): Face velocity must be strictly limited to 200 to 300 FPM200\text{ to }300\text{ FPM} (typically calculated at 200 CFM per square foot of gross filter area200\text{ CFM per square foot of gross filter area}). Exceeding 300 FPM300\text{ FPM} across pleated or fiberglass filters creates massive static pressure drops, pulls dust and particulates straight through the filter media, causes filter whistling, and can collapse the filter frame into the return plenum.

Step-by-Step Worked Engineering Calculations

Calculation 1: Sizing a Modular Ceiling Diffuser

Problem: A commercial conference room (24 ft×20 ft24\text{ ft} \times 20\text{ ft} with a 9-foot ceiling) requires 600 CFM600\text{ CFM} of cooling supply air. The engineer specifies an acoustic ceiling threshold of NC 30. The room is served by two identical 4-way square ceiling diffusers (300 CFM300\text{ CFM} each) centered in each half of the room (active room length per diffuser L=12 ftL = 12\text{ ft}). Using the manufacturer selection data below, select the appropriate diffuser neck size:

  • 8-inch Neck: At 300 CFM300\text{ CFM}: Neck Velocity = 860 FPM860\text{ FPM}, Ps=0.09 in. w.g.P_s = 0.09\text{ in. w.g.}, NC = 34, Throw (T50T_{50}) = 15 ft15\text{ ft}.
  • 10-inch Neck: At 300 CFM300\text{ CFM}: Neck Velocity = 550 FPM550\text{ FPM}, Ps=0.04 in. w.g.P_s = 0.04\text{ in. w.g.}, NC = 26, Throw (T50T_{50}) = 12 ft12\text{ ft}.
  • 12-inch Neck: At 300 CFM300\text{ CFM}: Neck Velocity = 380 FPM380\text{ FPM}, Ps=0.02 in. w.g.P_s = 0.02\text{ in. w.g.}, NC = 19, Throw (T50T_{50}) = 8 ft8\text{ ft}.

Step 1: Evaluate Acoustic Compliance (NC Limit)

  • Design maximum: NC 30.
  • The 8-inch neck generates NC 34, which violates the acoustic criteria and is rejected.
  • Both the 10-inch (NC 26) and 12-inch (NC 19) comply with sound requirements.

Step 2: Evaluate Throw-to-Length Ratio (T50/LT_{50} / L) for Comfort

  • For a 4-way ceiling diffuser, optimal ADPI (>80%) occurs when the T50/LT_{50} / L ratio is between 1.0 and 1.21.0\text{ and }1.2.
  • Active room distance: L=12 ftL = 12\text{ ft}.
  • 10-inch neck: T50/L=12 ft/12 ft=1.0T_{50} / L = 12\text{ ft} / 12\text{ ft} = 1.0 (Ideal comfort; air reaches the boundary wall at terminal velocity 50 FPM50\text{ FPM} without colliding or dumping).
  • 12-inch neck: T50/L=8 ft/12 ft=0.67T_{50} / L = 8\text{ ft} / 12\text{ ft} = 0.67 (Throw is too short; low velocity will cause the dense 55∘F55^\circ\text{F} supply air to drop prematurely into the room, creating stagnant zones near the walls).

Selection: The 10-inch neck is the correct engineering selection.


Calculation 2: Sizing a Residential Return Filter-Grille

Problem: A 3.5-ton residential heat pump in Little Rock, Arkansas, requires 1,400 CFM1,400\text{ CFM} (400 CFM/ton400\text{ CFM/ton}). The system utilizes a single central return air filter-grille located in a common hallway. To maintain low pressure drop and quiet operation, the contractor enforces a maximum face velocity limit of 250 FPM250\text{ FPM}. Calculate the minimum gross filter area required in square inches and select a standard commercial filter-grille size.

Step 1: Calculate minimum required free/face area in square feet

Area (ft2)=Airflow (CFM)Target Face Velocity (FPM)=1,400 CFM250 FPM=5.60 ft2\text{Area (ft}^2) = \frac{\text{Airflow (CFM)}}{\text{Target Face Velocity (FPM)}} = \frac{1,400\text{ CFM}}{250\text{ FPM}} = 5.60\text{ ft}^2

Step 2: Convert square feet to square inches

Area (in.2)=5.60 ft2×144 in.2/ft2=806.4 sq. inches\text{Area (in.}^2) = 5.60\text{ ft}^2 \times 144\text{ in.}^2/\text{ft}^2 = 806.4\text{ sq. inches}

Step 3: Evaluate standard commercial nominal filter sizes

  • Option A: 20"×30"=600 in.220" \times 30" = 600\text{ in.}^2 (4.17 ft2→Face Velocity=1,400/4.17=336 FPM4.17\text{ ft}^2 \rightarrow \text{Face Velocity} = 1,400 / 4.17 = 336\text{ FPM} — Violates the 250 FPM250\text{ FPM} limit).
  • Option B: 24"×30"=720 in.224" \times 30" = 720\text{ in.}^2 (5.00 ft2→Face Velocity=1,400/5.00=280 FPM5.00\text{ ft}^2 \rightarrow \text{Face Velocity} = 1,400 / 5.00 = 280\text{ FPM} — Marginal).
  • Option C: 24"×36"=864 in.224" \times 36" = 864\text{ in.}^2 (6.00 ft2→Face Velocity=1,400/6.00=233.3 FPM6.00\text{ ft}^2 \rightarrow \text{Face Velocity} = 1,400 / 6.00 = 233.3\text{ FPM} — Fully Compliant).

Result: The contractor must specify a 24"×36"24" \times 36" return filter-grille (or two 20"×20"20" \times 20" filter grilles providing 800+ in.2800+\text{ in.}^2) to satisfy the 250 FPM250\text{ FPM} acoustic and filtration benchmark.


Common Exam Traps & Regulatory Distinctions

  • Exam Trap: Grille vs. Register Definition: The licensing exam frequently tests the mechanical distinction between a grille and a register. Remember: A register always possesses an integral damper; a grille has no damper.
  • Exam Trap: Opposed Blade vs. Parallel Blade Damper Noise: Questions often ask which damper type is preferred for terminal volume trimming. Opposed blade dampers are preferred because they maintain a uniform velocity profile across the grille face, whereas parallel blade dampers direct air to one side, creating high-velocity whistling and jet distortion.
  • Exam Trap: The Coanda Effect Distance Limit: Questions regarding open ceiling designs frequently ask what happens when a ceiling diffuser is suspended far below the structural slab. If a diffuser is suspended more than 12 inches below a continuous ceiling plane, the Coanda effect is lost, causing the cool supply air to dump downward prematurely.
  • Exam Trap: Filter-Grille Velocity vs. Standard Return Grille Velocity: Candidates often apply the standard 450−500 FPM450-500\text{ FPM} return grille rule to filter-grilles. Filter-grilles must be restricted to 200−300 FPM200-300\text{ FPM} (or 2 CFM2\text{ CFM} per square inch of gross filter area) to prevent filter deformation, bypass, and severe static pressure loading.
Loading diagram...
Ceiling Diffuser Aerodynamic Jet Trajectory, Coanda Effect, and Occupied Zone
Test Your Knowledge

What primary aerodynamic failure occurs when a 4-way ceiling diffuser discharging 55°F air is installed in an exposed ceiling layout suspended 24 inches below the structural roof slab?

A

The air stream velocity accelerates exponentially, creating excessive face static pressure

B

The Noise Criteria rating drops below NC 15, causing acoustic resonance in the branch duct

C

The induction ratio increases beyond 30:1, overheating the occupied space

D

The Coanda effect is lost, causing the cold, dense supply air to dump prematurely into the occupied zone

Test Your Knowledge

A supply register catalog indicates an effective free area (A_k) of 0.85 sq. ft. If a balancing technician measures an average face velocity (V_k) of 600 FPM across the core using an anemometer, what is the volumetric airflow rate delivered?

A

425 CFM

B

510 CFM

C

600 CFM

D

705 CFM

Test Your Knowledge

Why are opposed blade dampers (OBD) preferred over parallel blade dampers (PBD) for terminal volume balancing registers?

A

Opposed blade dampers completely seal airtight against 5.0 in. w.g. static pressure

B

Opposed blade dampers are less expensive to fabricate and require zero mechanical maintenance

C

Opposed blade dampers maintain a symmetrical airflow pattern across the grille face and generate substantially less aerodynamic noise during modulation

D

Opposed blade dampers increase discharge air throw by deflecting the air stream sharply to one side

Test Your Knowledge

What is the maximum recommended face velocity across a central residential return filter-grille to prevent excessive static pressure drop, particulate blow-through, and acoustic whistling?

A

200 to 300 FPM

B

450 to 600 FPM

C

700 to 850 FPM

D

1,000 to 1,200 FPM

Sections you finish are checked off in the contents.