Using IFGC 2021 Table 402.4(2) (Schedule 40 metallic pipe, natural gas, inlet less than 2 psi, 0.5-inch w.c. drop, specific gravity 0.60), what is the smallest pipe that can supply an 80,000 Btu/h appliance 60 feet of developed length from the point of delivery? At 60 feet the table capacities are 65 cfh for 1/2 inch, 137 cfh for 3/4 inch, and 257 cfh for 1 inch. Assume 1,000 Btu per cubic foot.
- A1/2 inch
- B3/4 inch
- C1 inch
- D1-1/4 inch