Three neon-tubing transformers on one 120-volt primary circuit draw 7.2 amperes each and operate continuously. Using NEC 2017 600.5(B), 210.19(A)(1), 210.20(A), Table 310.15(B)(16), and 240.4(D), what is the smallest copper THWN conductor and standard breaker that will carry the load?
- A10 AWG copper and a 30-ampere breaker
- B12 AWG copper and a 20-ampere breaker
- C14 AWG copper and a 15-ampere breaker
- D8 AWG copper and a 50-ampere breaker