An existing one-family dwelling service is being upgraded to 200 amperes, 120/240-volt, single-phase, and the service conductors will carry the entire dwelling load. Using 310.15(B)(7) and 75°C copper terminations, what is the smallest service conductor permitted from Table 310.15(B)(16)?
- A1 AWG copper (130 amperes)
- B1/0 AWG copper (150 amperes)
- C2/0 AWG copper (175 amperes)
- D3/0 AWG copper (200 amperes)