R-404A suction at a −20°F freezer evaporator is 16 psig. At the compressor, after 80 ft of suction line, the pressure is 13 psig, which the P/T chart lists as −25°F. What is the equivalent suction-line temperature drop, and is it acceptable versus a 2°F design?
- A5°F — high; the line is undersized or too long
- B3 psig — report drop in psi only; temperature drop is not used
- C45°F — subtract −25 from +20
- D0°F — pressure drop does not change saturation temperature