Using NFPA 54 Table 6.3 (undiluted propane, 11.0 in. w.c. inlet, 0.5 in. w.c. drop, Schedule 40 metallic, capacities in thousands of Btu/h), what is the smallest listed pipe that will carry a 200,000 Btu/h load 50 feet from a second-stage regulator?
- A1/2 inch (122 thousand Btu/h at 50 feet)
- B3/4 inch (255 thousand Btu/h at 50 feet)
- C1 inch is the minimum regardless of load
- D2 inch, because propane always requires the next larger size