A dwelling has an 80,000 Btu/h furnace and a 40,000 Btu/h water heater on natural gas with a heating value of 1,000 Btu per cubic foot. The developed length to the more remote appliance is 40 feet. Using the same UMC table (less than 2 psi, 0.5 inch water-column drop, SG 0.60), capacities at 40 feet are: 1/2 inch = 81 CFH, 3/4 inch = 170 CFH. The branch that serves only the 40,000 Btu/h water heater must be at least which size?
- A1/2 inch, because 40 CFH is less than 81 CFH at the 40-foot longest length
- B3/8 inch, because 40 CFH always fits 3/8 inch
- C3/4 inch, because every appliance branch must match the main
- D1 inch, because water heaters require 1-inch connectors