Using the IFGC longest-length method and this excerpt of Table 402.4(2) (Schedule 40 metallic pipe, natural gas, inlet less than 2 psi, 0.5 inch w.c. drop) at 40 feet — 1/2 inch = 81 cfh, 3/4 inch = 170 cfh, 1 inch = 320 cfh — what is the smallest pipe that can supply a 100,000 Btu/h furnace (100 cfh at 1,000 Btu/cu ft) that is 40 feet of developed length from the meter?
- A3/8 inch
- B1/2 inch
- C3/4 inch
- D1 inch