A private dwelling has fixtures totaling 24 drainage fixture units on a common horizontal drain. If the designer must use a 1% slope instead of 2%, and the code multiplies allowable horizontal fixture-unit capacity by 0.8 at 1% slope, what adjusted load should be used when checking table capacity?
- A24 fixture units with no adjustment
- B30 fixture units (use 24 ÷ 0.8)
- C48 fixture units (double the load)
- D19.2 fixture units (use 0.8 × 24)