On a psychrometric chart, what does the dew-point temperature (DPT) represent for a given moist-air state point?
Psychrometrics
Question · Easy
Air at 75°F DBT and 50% RH has a humidity ratio of approximately 0.00925 lb_w/lb_da and an enthalpy of about 28.1 BTU/lb_da. If this air is sensibly heated to 95°F (no moisture added), what happens to the relative humidity?
Question · Medium
Chapter 1: Exam Overview, Reference Handbook & Engineering Foundations
1.1 NCEES Exam Specification, CBT Delivery & Reference Handbook Strategy
Study guide
A space requires 20,000 BTU/h of sensible cooling and 5,000 BTU/h of latent cooling. What is the sensible heat ratio (SHR) of the space load?
Engineering Exam Prep Podcast
Listen on Spotify
Podcast
Outdoor air at 95°F DBT and W = 0.018 lb_w/lb_da is mixed with return air at 75°F DBT and W = 0.010 lb_w/lb_da in the ratio 25% OA / 75% RA by mass. What is the mixed-air dry-bulb temperature?
A cooling coil has an entering condition of 80°F DBT / 67°F WBT and a leaving condition of 55°F DBT / 54°F WBT. The apparatus dew-point (ADP) is 50°F. What is the coil bypass factor (BF)?
Per ASHRAE 62.1-2022 Ventilation Rate Procedure, the breathing-zone outdoor airflow Vbz is computed as:
Loads
1.2 Engineering Units, Dimensional Analysis & Physical Property Lookups
An office zone has 25 occupants and 2,500 ft². Per ASHRAE 62.1-2022, Rp = 5 cfm/person and Ra = 0.06 cfm/ft² for offices. What is the breathing-zone outdoor airflow Vbz?
Under standard sea-level air conditions, the sensible heat factor for cfm-based load calculations is approximately 1.08. What does this constant represent?
An air-handling unit delivers 4,000 cfm of supply air at 55°F to a space maintained at 75°F. Assuming sea-level standard air, what is the sensible cooling capacity (BTU/h)?
1 ton of refrigeration is defined as the rate of heat removal equivalent to:
Refrigeration
1.3 Engineering Economics, Life Cycle Cost Analysis & Equipment Financial Evaluation
A vapor-compression refrigeration cycle operates with evaporator-exit enthalpy h1 = 110 BTU/lb, compressor-exit enthalpy h2 = 125 BTU/lb, and condenser-exit (and expansion-valve inlet) enthalpy h3 = 40 BTU/lb. What is the cooling COP?
EER and COP are related by which conversion factor?
A residential heat pump has a Heating Seasonal Performance Factor (HSPF2) of 8.5 BTU/Wh in the 2026-rated metric. What is the seasonal heating COP?
Per the EPA AIM Act Technology Transitions Rule, which GWP cap applies to NEW residential and light-commercial air conditioners and heat pumps installed on or after January 1, 2026?
1.4 Electrical Foundations, Motor Ratings & Variable Frequency Drives (VFDs)
ASHRAE Standard 15 classifies refrigerants by toxicity (A or B) and flammability (1, 2L, 2, 3). What is the safety classification of R-32 and R-454B that drives charge-limit and ventilation requirements in 2026 installations?
Codes
A centrifugal fan is operating at 1,200 rpm delivering 15,000 cfm at 3.0 in. wg static pressure with 12 bhp. If fan speed is increased to 1,500 rpm with the same impeller and air density, what is the new brake horsepower?
Equipment
A pump delivers 200 gpm at 80 ft of head running at 1,750 rpm. By the pump affinity laws (constant impeller diameter), what speed produces 250 gpm?
Net positive suction head available (NPSHa) is calculated as:
Chapter 2: Thermodynamics & Energy Balances
2.1 First and Second Laws of Thermodynamics & Open/Closed System Energy Balances
A cooling tower receives condenser water at 95°F and discharges it at 85°F while the ambient wet-bulb is 78°F. What are the tower's RANGE and APPROACH?
A counterflow heat exchanger has hot side 200 → 130°F and cold side 60 → 110°F. What is the log-mean temperature difference (LMTD)?
Heat Transfer
For a heat exchanger with fluid heat capacity rates Cmin and Cmax, effectiveness ε is defined as:
Air flows in a round duct at 2,000 cfm. To use the equal-friction method at a target of 0.10 in. wg per 100 ft, the engineer reads an 11-inch round duct. If the equivalent rectangular duct must be 8 inches deep, what width approximates the same friction and capacity?
Systems
Question · Hard
2.2 Thermodynamic Cycles: Carnot, Rankine, Brayton & Reversed Carnot Limit
The static-regain duct sizing method is preferred over equal-friction when:
Which of the following is NOT one of the three ventilation procedures defined in ASHRAE Standard 62.1-2022?
ASHRAE Standard 55-2023 thermal-comfort criteria are most commonly expressed using which two indices?
Per ASHRAE Standard 90.1-2022, water-cooled centrifugal chillers must meet minimum efficiency on TWO simultaneous metrics under a chosen path. What does the IPLV represent?
2.3 Gas & Vapor Property Evaluation: Steam Tables, Superheat & Subcooling
A chilled-water plant must reject 200 tons of cooling at the cooling tower while the chiller runs at COP = 5.5. What heat rejection rate (in tons) does the cooling tower see?
An absorption chiller using a lithium-bromide / water solution differs fundamentally from vapor-compression in that it:
A boiler delivers 5,000 lbm/h of saturated steam at 100 psia (h_g ≈ 1,187 BTU/lb) using feedwater at 200°F (h_f ≈ 168 BTU/lb). What is the boiler heat input rate to water (excluding stack losses)?
Which heat-transfer mechanism dominates between a person in a room and a cold window across the room?
2.4 Mass, Energy & Combustion Balances for HVAC Equipment
A 6-inch-thick fiberglass insulation has R-value of 19 (h·ft²·°F/BTU). What is the heat flux through this insulation when one face is at 80°F and the other at 30°F?
For a chilled-water coil with a 10°F water-side temperature rise, the rule-of-thumb gpm/ton is approximately:
Manual J residential load calculations are published by which organization and address what scope?
The Cooling Load Temperature Difference (CLTD) method, traditionally used by ASHRAE for opaque surfaces, accounts for which effect that simple ΔT-based conduction calculations miss?
Chapter 3: Psychrometrics, Moist Air Processes & Humidity Equipment
3.1 Psychrometric Properties: DBT, WBT, DPT, RH, Humidity Ratio & Enthalpy
Energy recovery ventilators (ERVs) differ from heat recovery ventilators (HRVs) in that ERVs:
Variable Air Volume (VAV) systems vary which parameter to match the cooling demand of each zone?
A pump operates at the intersection of its pump curve and the system curve. If a control valve closes partially, raising system curve resistance, the new operating point will have:
ASHRAE Standard 15 prescribes the maximum refrigerant charge in a high-probability occupancy based on RCL (Refrigerant Concentration Limit) and room volume. For an A1 refrigerant with RCL = 25 lb/Mcf in a 2,000 ft³ room, what is the maximum allowable charge?