A 50 Hz generator is rated 100 MVA, 11 kV, with subtransient reactance X'' = 0.20 pu. It is connected to a transformer rated 100 MVA, 11/132 kV with leakage reactance X = 0.10 pu. What is the subtransient short-circuit current for a symmetrical 3-phase fault at the high-voltage terminals of the transformer? (Assume pre-fault voltage is 1.0 pu)
- A1458 A
- B2525 A
- C4374 A
- D7575 A