The combustion triangle (fire triangle) identifies the three elements that must be present for combustion to occur. Which set lists all three?
Combustion Fundamentals
Question · Easy
Complete combustion of a hydrocarbon fuel such as natural gas, with sufficient oxygen, produces primarily which two products?
A combustion analyzer shows oxygen rising and carbon dioxide falling in the flue gas as a technician opens the primary air shutter. This relationship occurs because:
Combustion Analysis
Question · Medium
Trades Exam Prep Podcast
Listen on Spotify
Podcast
A technician clocks a furnace and finds it burns 10 cubic feet of natural gas in 6 minutes. With a heating value of 1,000 BTU per cubic foot, what is the approximate gross input?
Fuel Gases
Question · Hard
A technician clocks the gas meter using the 1-cubic-foot test dial and finds it takes 36 seconds for one revolution. Natural gas heating value is 1,000 BTU/ft3. What is the burner input?
The standard manifold (burner) gas pressure for a typical residential natural-gas furnace is approximately:
Propane (LP) differs from natural gas in several properties. Compared with natural gas, propane has:
Stoichiometric (perfect) combustion of natural gas requires approximately how much air per cubic foot of gas, and why is excess air added in practice?
On a combustion analyzer, the reading reported as 'CO air-free' (CO_af) is used instead of as-measured CO because it:
A combustion analyzer reports net stack temperature, oxygen, and combustion efficiency. The 'net' stack temperature used in steady-state efficiency is:
For a properly adjusted, non-condensing natural-gas furnace, a technician would expect flue-gas oxygen and CO air-free to fall within roughly which ranges?
A flame-rectification (flame-sensing) circuit proves the presence of a flame by detecting that the flame:
Gas Controls Ignition
In a hot-surface ignition (HSI) furnace, the igniter is typically made of silicon carbide or silicon nitride. Its primary function is to:
In the heating sequence of operation for an induced-draft furnace, what must occur immediately after the thermostat calls for heat and before the gas valve is energized?
A flame rollout switch on a gas furnace is a safety control that:
A standing-pilot furnace uses a thermocouple in the pilot flame. The thermocouple holds the pilot gas valve open by generating approximately:
A Category I gas appliance is best described as one that operates with:
Venting
A high-efficiency condensing furnace (around 90 percent-plus AFUE) is classified as a Category IV appliance and is typically vented with:
AFUE (Annual Fuel Utilization Efficiency) for a gas furnace represents:
Gas Equipment
An electric strip-heat element draws 20 amps at 240 volts. Using P = I x E, what is its power, and approximately how many BTU/h does it deliver (1 W = 3.412 BTU/h)?
Electric Heat
A heat sequencer in an electric furnace is used to:
Carbon monoxide (CO) is dangerous primarily because it:
Co Safety
When measuring combustion efficiency, a higher net stack temperature with all else equal results in:
At higher altitudes, gas-fired equipment input must usually be derated because:
A gas furnace orifice (spud) controls the fuel input primarily by:
A combustion analyzer should be set up (zeroed) in fresh air before testing. The main reason is to:
During combustion analysis on an atmospheric furnace, the technician finds O2 at 3 percent and CO air-free at 600 ppm. The most likely cause is:
A blue flame with sharp, well-defined inner cones on an atmospheric natural-gas burner generally indicates:
A yellow, lazy flame on a natural-gas burner most commonly indicates:
A pressure switch on an induced-draft furnace failed to close. With the inducer confirmed running, the next most likely cause to check is:
On a furnace using an intermittent pilot (spark-ignited pilot), if the pilot lights but the main burner never ignites, the most likely fault is in the:
The high-limit switch on a gas furnace protects the equipment by:
A furnace short-cycles on the high-limit switch (heats, then trips, then restarts). The most probable root cause is:
The temperature rise of a gas furnace is the difference between supply and return air temperatures. If the measured rise is above the manufacturer's rated range, the technician should suspect:
A 240-volt electric heating element has a resistance of 12 ohms. Using Ohm's law, what current does it draw, and what power does it dissipate?
Electric resistance heating elements are commonly protected from overheating (for example if airflow is lost) by a:
When measuring CO2 in flue gas, a higher CO2 reading (within safe CO limits) generally indicates:
An induced-draft (fan-assisted) furnace differs from an older atmospheric (natural-draft) furnace in that it:
The primary heat exchanger in a gas furnace can develop cracks. The chief safety concern with a cracked heat exchanger is that it can:
A common-vented system connects a furnace and a water heater into one chimney. A frequent venting problem after a high-efficiency furnace replaces the old furnace is that the:
Condensate produced by a condensing (Category IV) furnace is mildly acidic. Why does this matter for installation?
A combustion analyzer reads 80 percent combustion efficiency on an atmospheric furnace with 9 percent O2 and a net stack temperature of 350 degrees F. To raise the steady-state efficiency safely, the technician would generally try to:
Why must a flame sensor (flame rod) have a good electrical ground at the burner to function?
A redundant gas valve used on modern furnaces is designed so that:
What is the approximate higher heating value of propane (LP) per cubic foot?
Because propane is heavier than air (specific gravity greater than 1), a key safety consideration is that an LP leak will:
When converting a furnace from natural gas to propane, beyond changing orifices the technician must usually: