A enterprise data center consumes a total facility power of 2,400 kW, of which 1,600 kW is consumed directly by IT equipment (servers, storage, and networking devices), while the remaining 800 kW powers cooling systems, UPS losses, and lighting. What is the Power Usage Effectiveness (PUE) of this facility, and what is its ideal theoretical minimum?
- APUE = 1.50; ideal theoretical minimum is 1.0.
- BPUE = 0.67; ideal theoretical minimum is 0.0.
- CPUE = 2.00; ideal theoretical minimum is 1.0.
- DPUE = 1.25; ideal theoretical minimum is 0.5.