A loose-laid single-ply FPO flat roof is secured against wind uplift purely by gravel ballast (Kiesauflast Rundkies 16/32). In the corner zone, structural calculations determine a peak wind uplift suction force of w_k = 1.20 kN/m² (120 kg/m²). If the bulk density of rounded washed river gravel (Rundkies 16/32) is gamma = 18.0 kN/m³ (1,800 kg/m³), what is the minimum theoretical gravel layer thickness required to counteract this wind uplift, and what is the standard minimum practical layer thickness per ÖNORM B 3691?
- ATheoretical thickness d = 6.67 cm (0.067 m); practically specified as at least 7.0–8.0 cm…
- BTheoretical thickness d = 1.20 cm; practically specified as 2.0 cm.
- CTheoretical thickness d = 25.0 cm; practically specified as 30.0 cm.
- DTheoretical thickness d = 0.50 cm; practically specified as 1.0 cm.