9.3 Type III Recovery and Service Procedures

Key Takeaways

  • Low-pressure recovery: 25 mm Hg absolute (newer) or 25" Hg vacuum (older equipment)
  • Pressurize to 0 psig before opening a low-pressure system
  • Rupture disc bursts at 15 psig — one-time use, must be replaced after activation
  • Charge liquid into the evaporator, not the suction line
  • Never isolate a full charge from water flow — over-pressurization danger
Last updated: March 2026

9.3 Type III Recovery and Service Procedures

Recovery and service procedures for low-pressure systems differ significantly from high-pressure systems due to vacuum operation, large refrigerant charges, and the unique physical characteristics of low-pressure refrigerants.

Recovery Requirements for Low-Pressure Systems

Equipment AgeRequired Evacuation Level
Manufactured after November 15, 199325 mm Hg absolute
Manufactured before November 15, 199325 inches Hg vacuum

25 mm Hg absolute is a very deep vacuum — nearly complete evacuation of the system. This is measured with a micron gauge or absolute pressure gauge, NOT a standard compound gauge.

Understanding the Pressure Measurements

MeasurementValueMeaning
25 mm Hg absolute25 mm Hg above perfect vacuumVery deep vacuum (newer equipment)
25 inches Hg vacuum25 in. Hg below atmosphericLess deep vacuum (older equipment)
Perfect vacuum0 mm Hg absolute = 29.92 in. Hg vacuumNo gas molecules at all
Atmospheric760 mm Hg absolute = 0 in. Hg vacuum = 0 psigSea level pressure

Recovery Procedures for Low-Pressure Chillers

Step 1: Prepare for recovery

  • Shut down the chiller
  • Allow pressures to equalize
  • Connect recovery equipment to the chiller service connections
  • Ensure recovery cylinders have adequate capacity (low-pressure chillers often contain hundreds of pounds)

Step 2: Liquid recovery

  • Transfer liquid refrigerant from the evaporator and condenser shells
  • Low-pressure refrigerants are relatively easy to handle as liquid because they boil at high temperatures
  • Can often gravity-drain liquid into recovery containers in cooled environments

Step 3: Vapor recovery

  • After liquid is removed, use a recovery machine to pull remaining vapor
  • Continue until required evacuation level is reached (25 mm Hg absolute)
  • May need to apply gentle heat to the chiller shells to vaporize remaining liquid

Step 4: Verify evacuation

  • Use an absolute pressure gauge or micron gauge to verify the evacuation level
  • Allow the system to stabilize before taking the final reading
  • If the pressure rises above the required level, continue recovery

Before Opening a Low-Pressure System

Before opening a low-pressure appliance for service, the system must be pressurized to 0 psig (atmospheric pressure) to prevent:

  • Air rushing into the system when it is opened
  • Sudden pressure changes that could be dangerous

Important: The system is first recovered to the required level (25 mm Hg), then pressurized to 0 psig using recovered refrigerant or nitrogen before opening.

Charging Low-Pressure Systems

Charging a low-pressure chiller differs from high-pressure systems:

  • Refrigerant is added as liquid to the evaporator (not the suction line)
  • The liquid is introduced below the water tubes in the evaporator shell
  • Charging through the suction line could cause liquid slugging
  • Because the system is in vacuum, liquid will flash to vapor quickly
  • Large charges may take several hours to add

Rupture Disc Safety

Low-pressure chillers have rupture discs as a critical safety device:

  • Set to burst at 15 psig — to relieve pressure before it reaches dangerous levels
  • Since these systems normally operate in vacuum, 15 psig represents a significant over-pressure
  • Rupture discs are one-time use devices — they must be replaced after bursting
  • Never valve off or bypass the rupture disc during system operation
  • During repair, a pressure relief valve may temporarily substitute while the rupture disc is being replaced

Preventing Over-Pressurization

Low-pressure systems can become dangerously over-pressurized if:

  • The system is shut down and ambient temperature exceeds the refrigerant boiling point
  • Water side isolation causes the refrigerant to be heated by warm condenser water
  • NEVER isolate a chiller with a full charge and then shut off the water — the stored heat can cause pressure buildup
  • Always leave water flowing or recover the charge before extended shutdowns

For the Exam: Recovery to 25 mm Hg absolute for newer equipment. Pressurize to 0 psig before opening. Rupture disc bursts at 15 psig. Charge liquid into the evaporator. Never isolate a full charge from water flow during shutdown.

Test Your Knowledge

What is the required evacuation level for a low-pressure system manufactured after November 15, 1993?

A
B
C
D
Test Your Knowledge

At what pressure is the rupture disc on a low-pressure centrifugal chiller designed to burst?

A
B
C
D
Test Your Knowledge

Where is liquid refrigerant charged into a low-pressure centrifugal chiller?

A
B
C
D