9.3 Type III Recovery and Service Procedures
Key Takeaways
- Low-pressure recovery: 25 mm Hg absolute (newer) or 25" Hg vacuum (older equipment)
- Pressurize to 0 psig before opening a low-pressure system
- Rupture disc bursts at 15 psig — one-time use, must be replaced after activation
- Charge liquid into the evaporator, not the suction line
- Never isolate a full charge from water flow — over-pressurization danger
9.3 Type III Recovery and Service Procedures
Recovery and service procedures for low-pressure systems differ significantly from high-pressure systems due to vacuum operation, large refrigerant charges, and the unique physical characteristics of low-pressure refrigerants.
Recovery Requirements for Low-Pressure Systems
| Equipment Age | Required Evacuation Level |
|---|---|
| Manufactured after November 15, 1993 | 25 mm Hg absolute |
| Manufactured before November 15, 1993 | 25 inches Hg vacuum |
25 mm Hg absolute is a very deep vacuum — nearly complete evacuation of the system. This is measured with a micron gauge or absolute pressure gauge, NOT a standard compound gauge.
Understanding the Pressure Measurements
| Measurement | Value | Meaning |
|---|---|---|
| 25 mm Hg absolute | 25 mm Hg above perfect vacuum | Very deep vacuum (newer equipment) |
| 25 inches Hg vacuum | 25 in. Hg below atmospheric | Less deep vacuum (older equipment) |
| Perfect vacuum | 0 mm Hg absolute = 29.92 in. Hg vacuum | No gas molecules at all |
| Atmospheric | 760 mm Hg absolute = 0 in. Hg vacuum = 0 psig | Sea level pressure |
Recovery Procedures for Low-Pressure Chillers
Step 1: Prepare for recovery
- Shut down the chiller
- Allow pressures to equalize
- Connect recovery equipment to the chiller service connections
- Ensure recovery cylinders have adequate capacity (low-pressure chillers often contain hundreds of pounds)
Step 2: Liquid recovery
- Transfer liquid refrigerant from the evaporator and condenser shells
- Low-pressure refrigerants are relatively easy to handle as liquid because they boil at high temperatures
- Can often gravity-drain liquid into recovery containers in cooled environments
Step 3: Vapor recovery
- After liquid is removed, use a recovery machine to pull remaining vapor
- Continue until required evacuation level is reached (25 mm Hg absolute)
- May need to apply gentle heat to the chiller shells to vaporize remaining liquid
Step 4: Verify evacuation
- Use an absolute pressure gauge or micron gauge to verify the evacuation level
- Allow the system to stabilize before taking the final reading
- If the pressure rises above the required level, continue recovery
Before Opening a Low-Pressure System
Before opening a low-pressure appliance for service, the system must be pressurized to 0 psig (atmospheric pressure) to prevent:
- Air rushing into the system when it is opened
- Sudden pressure changes that could be dangerous
Important: The system is first recovered to the required level (25 mm Hg), then pressurized to 0 psig using recovered refrigerant or nitrogen before opening.
Charging Low-Pressure Systems
Charging a low-pressure chiller differs from high-pressure systems:
- Refrigerant is added as liquid to the evaporator (not the suction line)
- The liquid is introduced below the water tubes in the evaporator shell
- Charging through the suction line could cause liquid slugging
- Because the system is in vacuum, liquid will flash to vapor quickly
- Large charges may take several hours to add
Rupture Disc Safety
Low-pressure chillers have rupture discs as a critical safety device:
- Set to burst at 15 psig — to relieve pressure before it reaches dangerous levels
- Since these systems normally operate in vacuum, 15 psig represents a significant over-pressure
- Rupture discs are one-time use devices — they must be replaced after bursting
- Never valve off or bypass the rupture disc during system operation
- During repair, a pressure relief valve may temporarily substitute while the rupture disc is being replaced
Preventing Over-Pressurization
Low-pressure systems can become dangerously over-pressurized if:
- The system is shut down and ambient temperature exceeds the refrigerant boiling point
- Water side isolation causes the refrigerant to be heated by warm condenser water
- NEVER isolate a chiller with a full charge and then shut off the water — the stored heat can cause pressure buildup
- Always leave water flowing or recover the charge before extended shutdowns
For the Exam: Recovery to 25 mm Hg absolute for newer equipment. Pressurize to 0 psig before opening. Rupture disc bursts at 15 psig. Charge liquid into the evaporator. Never isolate a full charge from water flow during shutdown.
What is the required evacuation level for a low-pressure system manufactured after November 15, 1993?
At what pressure is the rupture disc on a low-pressure centrifugal chiller designed to burst?
Where is liquid refrigerant charged into a low-pressure centrifugal chiller?