8.3 Type II: Leak Detection and Repair
Key Takeaways
- Leak triggers: 10% comfort cooling, 20% commercial, 30% industrial — repairs within 30 days
- Electronic detectors find general area; bubble solution pinpoints exact location
- After repair: nitrogen pressure test → deep vacuum to 500 microns → recharge
- Non-condensable gases in a system cause high head pressure
- A system holding below 500 microns is properly evacuated and leak-free
8.3 Type II: Leak Detection and Repair
Leak detection and repair are among the most critical skills for Type II technicians. High-pressure systems are the most common in the field, and proper leak management prevents environmental damage, reduces costs, and maintains system performance.
Leak Rate Triggers for Type II Systems
| Equipment Type | Trigger Rate | Charge Threshold |
|---|---|---|
| Comfort cooling (residential/commercial AC) | 10% | 50 lbs ODS / 15 lbs HFC (2026) |
| Commercial refrigeration | 20% | 50 lbs ODS / 15 lbs HFC (2026) |
| Industrial process refrigeration | 30% | 50 lbs ODS / 15 lbs HFC (2026) |
Leak Detection Best Practices for High-Pressure Systems
Step 1: Determine if a leak exists
- Review service history and refrigerant addition records
- Calculate annualized leak rate
- Perform a standing pressure test if needed
Step 2: Locate the leak
- Use an electronic leak detector (most effective for general area)
- Move probe slowly (1 inch/second) along all connections, fittings, and joints
- Check the lowest points first — refrigerant is heavier than air
- Use bubble solution to pinpoint exact leak location after the area is identified
- Common leak locations: Schrader valve cores, flare connections, brazed joints, service valve packing, condenser coils, evaporator coils
Step 3: Repair the leak
- Recover the refrigerant to the required level
- If brazing: evacuate and nitrogen-purge during brazing
- Complete the repair
- Pressure test with dry nitrogen
- Evacuate the system (pull a deep vacuum)
- Recharge with the correct refrigerant
- Verify the repair with a follow-up leak test
Nitrogen Pressure Testing After Repair
After completing a leak repair:
- Pressurize the system with dry nitrogen to the system's rated working pressure (or manufacturer's specification)
- Never exceed the rated pressure
- Always use a pressure regulator on the nitrogen tank
- Allow the system to sit for a minimum of 10-15 minutes (longer for larger systems)
- Monitor the pressure gauge for any drop
- If pressure drops, the leak was not fully repaired — relocate and fix
System Evacuation After Repair
After a successful pressure test:
- Release the nitrogen from the system
- Connect a vacuum pump
- Pull a deep vacuum to 500 microns (or manufacturer specification)
- Hold the vacuum for a minimum of 10 minutes
- If the vacuum rises above 1,000 microns, there is still moisture or a leak
- A system that holds below 500 microns is properly evacuated and leak-free
Common High-Pressure System Problems
| Symptom | Possible Cause | Action |
|---|---|---|
| High head pressure | Dirty condenser, overcharge, non-condensables | Clean condenser, check charge, purge NCGs |
| Low suction pressure | Undercharge (leak), restricted metering device | Check for leaks, inspect TXV |
| Icing at metering device | Moisture in system | Replace filter-drier, evacuate properly |
| Compressor short cycling | Low charge, faulty controls | Check for leaks, verify controls |
| High superheat | Undercharge, restricted liquid line | Check for leaks, inspect filter-drier |
| Low superheat | Overcharge, faulty TXV | Check charge, inspect TXV |
For the Exam: After repair: nitrogen pressure test → release nitrogen → deep vacuum to 500 microns → hold test → recharge. Non-condensable gases (NCGs) in a system cause high head pressure. The system should hold below 500 microns during a standing vacuum test.
What should be the target vacuum level when evacuating a system after a leak repair?
What causes abnormally high head (discharge) pressure in a high-pressure system?
After completing a leak repair on a high-pressure system, the correct sequence of steps is: