Controls, Instrumentation, and Uncertainty Cases
Key Takeaways
- Read a controls prompt by naming the loop pieces: plant, sensor, signal conditioning, controller, actuator, feedback, and disturbance.
- First-order systems G(s) = K/(tau*s + 1) are defined by gain K and time constant tau; second-order systems add natural frequency and damping ratio.
- Accuracy, precision, resolution, sensitivity, bias, and repeatability are distinct FE terms — an instrument can be precise yet biased.
- Uncertainty in products and quotients combines by relative (RSS) terms; in sums and differences it combines by absolute terms.
- The Nyquist minimum sampling rate is twice the highest meaningful signal frequency; sampling below it causes aliasing.
Treat the loop as a system
A control or instrumentation prompt describes a chain: physical variable, sensor, signal conditioning, controller, actuator, plant, feedback, and disturbance. Name those pieces before calculating. A temperature controller may use a thermocouple, amplifier, digital controller, control valve, heat exchanger, and outlet-temperature feedback. A speed controller may use an encoder, motor drive, rotating inertia, and load-torque disturbance.
FE controls questions are largely recognition based. A transfer function relates output to input in the Laplace domain for zero initial conditions. 2% of final value in one tau and is essentially settled by about 4*tau. A second-order system adds natural frequency omega_n and damping ratio zeta: zeta < 1 is underdamped (overshoot and ringing), zeta = 1 is critically damped, zeta > 1 is overdamped. Feedback reshapes the closed-loop response and can cut steady-state error, but a pole with a positive real part means an unstable response.
| Prompt cue | Concept | Exam action |
|---|---|---|
| G(s) = K/(tau*s + 1) | First-order response | Read off K and tau |
| Overshoot after a step | Underdamped 2nd order | Use damping-ratio logic |
| Output fed to summing junction | Feedback | Build closed-loop denominator |
| Pole with positive real part | Instability | Pick the unstable response |
| Repeated readings with offset | Bias | Calibrate / correct |
| False low-frequency tone | Aliasing | Raise sampling or filter input |
Worked problem: first-order step response
A thermocouple-amplifier chain has transfer function G(s) = 5/(2s + 1). Reading the standard form K/(taus + 1) gives K = 5 and tau = 2 s. After a unit step, the output rises toward 5; at t = tau = 2 s it has reached 0.6325 = 3.16, and it is about 98% settled by 4tau = 8 s. If the prompt asks for the value at t = 4 s (= 2tau), the response fraction is 1 - e^(-2) = 0.865, so output = 0.865*5 = 4.32.
Measurement vocabulary and uncertainty
Instrumentation items are vocabulary traps. Accuracy is closeness to the true value; precision is repeatability; resolution is the smallest detectable increment; sensitivity is output change per input change; bias is a systematic offset. A transducer reading 103 kPa against a 100 kPa standard with tight scatter is biased, not imprecise. A device can be precise but inaccurate; a display can have fine resolution yet poor accuracy if the sensor or calibration is weak.
Uncertainty propagation depends on the operation. For a sum or difference of independent quantities, combine absolute uncertainties by root-sum-square: u_R = sqrt(u_a^2 + u_b^2). For a product or quotient, combine relative uncertainties: (u_R/R) = sqrt((u_a/a)^2 + (u_b/b)^2). For a power, R = x^n gives (u_R/R) = |n|(u_x/x). Worked case: power P = VI with V = 12.0 V ±2% and I = 3.0 A ±3%. Relative uncertainty in P = sqrt(0.02^2 + 0.03^2) = sqrt(0.0004 + 0.0009) = sqrt(0.0013) = 0.0361 ≈ 3.6%, so P = 36.0 W ±1.30 W.
Sensors, sampling, and signal conditioning
Sensor choice follows the measured variable and environment. Thermocouples tolerate wide ranges but need cold-junction compensation; RTDs are accurate over moderate ranges; strain-gage load cells need bridge circuits and amplification; orifice and Venturi meters infer flow from pressure drop; encoders measure position and speed digitally. Signal conditioning amplifies small outputs, filters unwanted frequencies, isolates, linearizes, and digitizes. Sampling must capture the highest meaningful frequency: the Nyquist minimum is twice that frequency, and practical systems add margin to avoid aliasing.
A vibration signal with content to 450 Hz needs sampling of at least 900 Hz.
Worked problem: closed-loop gain and second-order parameters
A unity-feedback loop has forward transfer function G(s) and feedback H(s) = 1. The closed-loop transfer function is T(s) = G/(1 + GH). If G(s) = K/(s(s + 4)), the closed-loop denominator is s^2 + 4s + K. Comparing to the standard form s^2 + 2zetaomega_ns + omega_n^2, we read omega_n = sqrt(K) and 2zeta*omega_n = 4, so zeta = 2/sqrt(K). For K = 4, omega_n = 2 rad/s and zeta = 1 (critically damped — no overshoot). 5 (underdamped — the step response overshoots and rings).
This shows the FE-tested trade-off: raising loop gain speeds the response and shrinks steady-state error but reduces damping, eventually causing overshoot and, if a pole crosses into the right half-plane, instability.
Worked problem: full-scale versus reading uncertainty
A pressure gauge is rated ±0.5% of full scale with a full-scale span of 500 kPa, and it reads 120 kPa. The absolute uncertainty is fixed by the span: 0.005 * 500 = ±2.5 kPa, regardless of the reading. As a percent of the reading, that is 2.5/120 = 2.1% — much larger than 0.5%. Had the spec said ±0.5% of reading, the uncertainty would be only 0.005 * 120 = ±0.6 kPa. The FE distractor applies the 0.5% to the reading rather than the span. Always check whether a tolerance is percent-of-full-scale (constant absolute error) or percent-of-reading (constant relative error) before reporting an uncertainty.
Uncertainty-propagation quick rules
- Sums/differences (R = A ± B): combine absolute uncertainties in quadrature, u_R = √(u_A² + u_B²).
- Products/quotients (R = AB or A/B): combine relative uncertainties in quadrature, (u_R/R) = √((u_A/A)² + (u_B/B)²).
- Percent of full scale gives a constant absolute error; percent of reading gives a constant relative error.
A first-order system has G(s) = 5/(2s + 1). What are its steady-state gain and time constant?
Power P = V*I uses V = 12.0 V ±2% and I = 3.0 A ±3% (independent). What is the relative uncertainty in P?
A pressure transducer repeatedly reads 103 kPa when a calibrated standard reads 100 kPa, with very little scatter. Which term best describes the dominant error?
A vibration signal contains useful content up to 450 Hz. What is the minimum sampling frequency the Nyquist criterion requires?