Free Practice Questions for ITC Level II
Exam-style questions and explanations by OpenExamPrep.
Loading practice questions...
Explore More ITC Thermography Certifications
Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.
Key Facts: ITC Level II Exam
>15°C
NETA Major Discrepancy (similar components)
ANSI/NETA MTS Table 100.18
40%
Minimum Load for Electrical IR
NFPA 70B 7.4.5
0.98
Water Emissivity (8–14 µm)
ITC Reference
10°C
Min ΔT for Building Envelope Survey
ASTM C1060
5 params
Required Camera Parameters
ITC Level II
80%
Infraspection Pass Mark (open book)
infraspection.com
The Certified Infrared Thermographer Level II certification from ITC / Infraspection Institute validates advanced quantitative IR thermography competency. Level II thermographers apply emissivity correction (reference emitter, tape, paint, and direct methods), measure reflected apparent temperature, correct for IR window transmittance, and classify findings per ANSI/NETA MTS Table 100.18 and ASTM C1060 guidance. They also perform trending and baseline comparison, supervise Level I inspectors, and produce complete inspection reports with severity classifications and corrective action recommendations.
Sample ITC Level II Practice Questions
Try these sample questions to review concepts for the ITC Level II exam. Each question includes a detailed explanation. Start the interactive quiz above for the full 162+ question experience with AI tutoring.
1A thermographer measures a surface temperature of 85°C on a motor with an assumed emissivity of 0.95. The actual surface is bare aluminum with an emissivity of 0.05. The reflected temperature is 22°C. What is the most accurate statement about this measurement?
2Which emissivity correction method is MOST appropriate when you cannot touch or coat the surface being inspected?
3A Level II thermographer inspects electrical switchgear through a germanium IR window rated at 80% transmittance across the 8-14 um band. The camera measures 68°C on a busbar. What correction must be applied?
4Using the similar-components column of ANSI/NETA Table 100.18, a busbar connection measures 2°C above a similar connection under similar loading. Which recommended action applies?
5When setting up a camera for an outdoor inspection on a cold day (ambient 5°C), which parameters must the thermographer enter to ensure accurate temperature measurement?
6Black electrical tape of emissivity 0.95 is applied to a painted pipe and allowed to equilibrate. With the camera emissivity set to 0.95 the tape reads 51°C and the adjacent bare paint reads 48°C. What is the correct next step to find the paint emissivity?
7ISO 18434-1 governs infrared thermography within machinery condition monitoring. What does it provide for judging the severity of a hot bearing housing?
8A thermographer compares two images of the same circuit breaker taken six months apart. The first shows a 4°C difference against a similar breaker; the current image shows 12°C under the same load. The BEST interpretation is:
9What is the primary purpose of establishing a thermal baseline for electrical switchgear?
10Which of the following emissivity values is MOST accurate for polished stainless steel?
About the ITC Level II Exam
The ITC / Infraspection Institute Level II Certified Infrared Thermographer exam tests advanced quantitative thermography skills including precise temperature measurement with emissivity correction, severity classification per ANSI/NETA MTS Table 100.18, trending analysis, and QA/QC of Level I inspector work.
Exam sponsor: Infrared Training Center (ITC) / Infraspection Institute. The requirements and fees below concern the certification or admission exam, separate from our free practice resources.
Assessment
Question count not published by the exam provider
Time Limit
Not published by ITC or Infraspection
Passing Score
80% (Infraspection open-book exam); ITC cut score not published
Exam / Certification Fees
Bundled with the Level II course (not published separately)
Exam sponsor websiteFees, eligibility, and exam policies can change. Confirm them with the exam sponsor before applying or paying.
Our practice resources: topics covered
We aim to reflect publicly available exam outlines and topic information in our study resources. Coverage, format, and difficulty may differ from the actual exam, and we cannot guarantee that every detail is accurate or current. Confirm exam requirements, fees, and policies with the official exam sponsor.
Emissivity Correction & Measurement Setup
Reference emitter, tape, paint, and direct methods; reflected apparent temperature; IR window transmittance; camera parameter setup
Severity Classification Standards
ANSI/NETA MTS Table 100.18 thermographic survey criteria (similar-component and over-ambient ΔT bands), NFPA 70B minimum-load and interval rules, ASTM C1060 building envelope ΔT requirements
Data Analysis & Pattern Interpretation
Electrical fault patterns, mechanical defect signatures, building envelope anomalies, steam system inspection
Trending & Baseline Comparison
Establishing baselines, rate-of-change analysis, trend escalation criteria, multi-year data analysis
QA/QC of Level I Work
Parameter verification, equipment identification review, coverage completeness, finding reclassification
Reporting Standards & Professional Ethics
Report content requirements, image documentation, professional ethics, client communication
Preparing for the ITC Level II Exam
What You Need to Know
- Passing score: 80% (Infraspection open-book exam); ITC cut score not published
- Assessment: Question count not published by the exam provider
- Time limit: Not published by ITC or Infraspection
- Exam / certification fees: Bundled with the Level II course (not published separately) Official sources
Using Our Practice Resources
- Work through all 162 available questions
- Review every answer and explanation
- Track weak areas and revisit them
- Use our AI tutor for tough concepts
ITC Level II: Suggested Study Strategy
Frequently Asked Questions
What is the ITC Level II thermographer exam?
The ITC (Infrared Training Center) / Infraspection Institute Level II Certified Infrared Thermographer exam validates advanced quantitative IR thermography skills. Level II thermographers must demonstrate mastery of emissivity correction methods, severity classification per ANSI/NETA MTS Table 100.18, trending and baseline analysis, and QA/QC review of Level I work. The exam covers electrical, mechanical, and building envelope thermography applications.
What emissivity correction methods are tested at Level II?
Level II exams cover four emissivity correction methods: (1) Reference emitter — applying tape or paint and iterating camera emissivity until surfaces read the same; (2) Contact thermometer — measuring true temperature and back-calculating emissivity; (3) Reflected apparent temperature (RAT) — using a crumpled foil reflector to measure background radiation without touching the surface; and (4) Direct measurement using camera software with published emissivity tables. Polished metals (ε=0.05–0.15), oxidized metals (ε=0.30–0.80), and paints/plastics (ε=0.85–0.95) are key material groups.
What are the ANSI/NETA MTS severity criteria for electrical thermography?
ANSI/NETA MTS Table 100.18 classifies anomalies by ΔT. Against a similar component under similar load: 1–3 °C = possible deficiency (warrants investigation), 4–15 °C = probable deficiency (repair as time permits), above 15 °C = major discrepancy (repair immediately). Over ambient air: 1–10 °C possible deficiency, 11–20 °C probable deficiency, 21–40 °C monitor until corrective measures can be accomplished, above 40 °C major discrepancy. There are no numbered priority levels; NETA notes the bands are reasonable guidelines and that temperature rise scales roughly with the square of current.
How does Level II differ from Level I thermography certification?
Level I thermographers perform qualitative or limited quantitative scanning under supervision. Level II adds: full quantitative temperature measurement with emissivity and atmospheric corrections, severity classification against NETA/ISO/ASHRAE standards, trending and baseline comparison across multiple inspections, QA/QC review and sign-off authority for Level I data, and authorship of complete formal inspection reports with corrective action recommendations.
What does the ITC Level II exam cover for building envelope thermography?
Building envelope topics include the ASTM C1060 suggested minimum ΔT of 10°C (18°F) interior-exterior for 4 hours for meaningful wall inspections, interior mode during heating season for insulation defect detection, flat roof inspection protocols (1–4 hours post-sunset, wind <15 mph per ASTM C1153), air infiltration detection using blower door combined with IR, thermal bridging through structural framing, and interpretation of warm/cool pattern signatures for moisture, air leakage, and insulation defects.