100+ Free ITC Level II Practice Questions
Pass your Certified Infrared Thermographer Level II exam on the first try — instant access, no signup required.
A thermographer measures a surface temperature of 85°C on a motor with an assumed emissivity of 0.95. The actual surface is bare aluminum with an emissivity of 0.05. The reflected temperature is 22°C. What is the most accurate statement about this measurement?
Key Facts: ITC Level II Exam
P1
ΔT >35°C vs. Reference
NETA ATS
40%
Minimum Load for Electrical IR
Industry Standard
0.98
Water Emissivity (8–14 µm)
ITC Reference
10°C
Min ΔT for Building Envelope
ASHRAE
5 params
Required Camera Parameters
ITC Level II
$595
Exam Fee
Infraspection Institute
The Certified Infrared Thermographer Level II certification from ITC / Infraspection Institute validates advanced quantitative IR thermography competency. Level II thermographers apply emissivity correction (reference emitter, tape, paint, and direct methods), measure reflected apparent temperature, correct for IR window transmittance, and classify findings per NETA ATS (P1–P4), ISO 18434-1, and ASHRAE guidelines. They also perform trending and baseline comparison, supervise Level I inspectors, and produce complete inspection reports with severity classifications and corrective action recommendations.
Sample ITC Level II Practice Questions
Try these sample questions to test your ITC Level II exam readiness. Each question includes a detailed explanation. Start the interactive quiz above for the full 100+ question experience with AI tutoring.
1A thermographer measures a surface temperature of 85°C on a motor with an assumed emissivity of 0.95. The actual surface is bare aluminum with an emissivity of 0.05. The reflected temperature is 22°C. What is the most accurate statement about this measurement?
2Which emissivity correction method is MOST appropriate when you cannot touch or coat the surface being inspected?
3A Level II thermographer is inspecting electrical switchgear through a polycarbonate IR window rated at 80% transmittance in the 8–14 µm band. The camera measures 68°C on a busbar. What correction must be applied?
4According to the NETA ATS standard for electrical equipment, a temperature difference of 35°C above a similar component under similar load is classified as:
5When setting up a camera for an outdoor inspection on a cold day (ambient 5°C), which parameters must the thermographer enter to ensure accurate temperature measurement?
6A thermographer uses the reference emitter method to determine emissivity of a painted pipe. A piece of black tape is applied to the pipe, and after thermal equilibration the tape reads 48°C while the adjacent bare pipe reads 51°C. The emissivity of the pipe surface is approximately:
7ISO 18434-1 defines severity criteria for rotating machinery based on absolute surface temperatures. Which temperature zone typically triggers immediate corrective action for bearing housings?
8A thermographer is comparing two thermal images of the same circuit breaker taken six months apart. The first image shows a 12°C differential; the current image shows a 28°C differential under the same load conditions. The BEST interpretation is:
9What is the primary purpose of establishing a thermal baseline for electrical switchgear?
10Which of the following emissivity values is MOST accurate for polished stainless steel?
About the ITC Level II Exam
The ITC / Infraspection Institute Level II Certified Infrared Thermographer exam tests advanced quantitative thermography skills including precise temperature measurement with emissivity correction, severity classification per NETA ATS and ISO 18434 standards, trending analysis, and QA/QC of Level I inspector work.
Questions
100 scored questions
Time Limit
3 hours
Passing Score
75%
Exam Fee
$595 (Infrared Training Center (ITC) / Infraspection Institute)
ITC Level II Exam Content Outline
Emissivity Correction & Measurement Setup
Reference emitter, tape, paint, and direct methods; reflected apparent temperature; IR window transmittance; camera parameter setup
Severity Classification Standards
NETA ATS Priority 1–4 criteria, ISO 18434-1 rotating machinery zones, ASHRAE building envelope ΔT requirements
Data Analysis & Pattern Interpretation
Electrical fault patterns, mechanical defect signatures, building envelope anomalies, steam system inspection
Trending & Baseline Comparison
Establishing baselines, rate-of-change analysis, trend escalation criteria, multi-year data analysis
QA/QC of Level I Work
Parameter verification, equipment identification review, coverage completeness, finding reclassification
Reporting Standards & Professional Ethics
Report content requirements, image documentation, professional ethics, client communication
How to Pass the ITC Level II Exam
What You Need to Know
- Passing score: 75%
- Exam length: 100 questions
- Time limit: 3 hours
- Exam fee: $595
Keys to Passing
- Complete 500+ practice questions
- Score 80%+ consistently before scheduling
- Focus on highest-weighted sections
- Use our AI tutor for tough concepts
ITC Level II Study Tips from Top Performers
Frequently Asked Questions
What is the ITC Level II thermographer exam?
The ITC (Infrared Training Center) / Infraspection Institute Level II Certified Infrared Thermographer exam validates advanced quantitative IR thermography skills. Level II thermographers must demonstrate mastery of emissivity correction methods, severity classification per NETA ATS and ISO 18434-1 standards, trending and baseline analysis, and QA/QC review of Level I work. The exam covers electrical, mechanical, and building envelope thermography applications.
What emissivity correction methods are tested at Level II?
Level II exams cover four emissivity correction methods: (1) Reference emitter — applying tape or paint and iterating camera emissivity until surfaces read the same; (2) Contact thermometer — measuring true temperature and back-calculating emissivity; (3) Reflected apparent temperature (RAT) — using a crumpled foil reflector to measure background radiation without touching the surface; and (4) Direct measurement using camera software with published emissivity tables. Polished metals (ε=0.05–0.15), oxidized metals (ε=0.30–0.80), and paints/plastics (ε=0.85–0.95) are key material groups.
What are the NETA ATS severity criteria for electrical thermography?
NETA ATS classifies electrical anomalies by temperature difference (ΔT) vs. a similar reference component under similar load: Priority 4 (ΔT 1–10°C) = monitor at next inspection; Priority 3 (ΔT 11–20°C) = schedule repair at next outage; Priority 2 (ΔT 21–35°C) = repair before next maintenance or within 24 hours; Priority 1 (ΔT >35°C) = immediate action, consider de-energizing. Minimum load for valid electrical IR inspection is 40% of rated capacity.
How does Level II differ from Level I thermography certification?
Level I thermographers perform qualitative or limited quantitative scanning under supervision. Level II adds: full quantitative temperature measurement with emissivity and atmospheric corrections, severity classification against NETA/ISO/ASHRAE standards, trending and baseline comparison across multiple inspections, QA/QC review and sign-off authority for Level I data, and authorship of complete formal inspection reports with corrective action recommendations.
What does the ITC Level II exam cover for building envelope thermography?
Building envelope topics include ASHRAE minimum ΔT of 10°C (18°F) interior-exterior for meaningful wall inspections, interior mode during heating season for insulation defect detection, flat roof inspection protocols (1–4 hours post-sunset, wind <15 mph per ASTM C1153), air infiltration detection using blower door combined with IR, thermal bridging through structural framing, and interpretation of warm/cool pattern signatures for moisture, air leakage, and insulation defects.