When installing gas-fired hydronic boilers at elevations above 2,000 feet in Arizona (e.g. Flagstaff at ~7,000 ft), at what rate must the boiler fuel BTUH input rating be de-rated unless specified otherwise by the manufacturer?
- A1% per 1,000 feet above sea level
- B4% per 1,000 feet above sea level starting at sea level
- C4% per 1,000 feet above 2,000 feet elevation
- D10% per 1,000 feet above 5,000 feet elevation