During a system inspection, a technician notes a high head pressure, high subcooling (22°F), high superheat (35°F), and low suction pressure on a system equipped with a thermostatic expansion valve. What is the most probable fault?
- ARefrigerant system overcharge
- BEvaporator fan motor running backward
- CLiquid line filter-drier restriction or clogged TEV inlet screen
- DNon-condensable air trapped in the condenser coil