Ungrounded circuit conductors rated 100 A are upsized from 3 AWG copper to 1/0 AWG copper (an increase in circular mil area from 52,620 CM to 105,600 CM, double the size) to compensate for voltage drop. Under NEC 2017 Article 250.122(B), how must the copper equipment grounding conductor (originally 8 AWG copper, 16,510 CM) be adjusted?
- AIt can remain at 8 AWG copper because overcurrent device size did not change
- BIt must be upsized to 1/0 AWG copper to match the ungrounded conductors
- CIt can be reduced to 10 AWG copper
- DIt must be upsized proportionally in circular mil area to approximately 6 AWG copper (33,…