A short-circuit test is performed on the high-voltage side of a 100 kVA, 11,000/400 V distribution transformer with the low-voltage terminals short-circuited. The instruments record V_sc = 550 V, I_sc = 9.09 A (rated HV current), and P_sc = 1,200 W. What are the equivalent resistance R_eq and equivalent reactance X_eq referred to the high-voltage winding?
- AR_eq = 1.20 ohms, X_eq = 5.50 ohms
- BR_eq = 60.50 ohms, X_eq = 14.52 ohms
- CR_eq = 14.52 ohms, X_eq = 58.74 ohms
- DR_eq = 14.52 ohms, X_eq = 0 ohms