A thermographer measures a surface temperature of 85°C on a motor with an assumed emissivity of 0.95. The actual surface is bare aluminum with an emissivity of 0.05. The reflected temperature is 22°C. What is the most accurate statement about this measurement?
Emissivity Correction
Question · Hard
Which emissivity correction method is MOST appropriate when you cannot touch or coat the surface being inspected?
Question · Medium
Introduction & Exam Overview
1.1 About the Level II Exam
Study guide
A Level II thermographer inspects electrical switchgear through a germanium IR window rated at 80% transmittance across the 8-14 um band. The camera measures 68°C on a busbar. What correction must be applied?
Camera Parameter Setup
Trades Exam Prep Podcast
Listen on Spotify
Podcast
Using the similar-components column of ANSI/NETA Table 100.18, a busbar connection measures 2°C above a similar connection under similar loading. Which recommended action applies?
Severity Criteria
When setting up a camera for an outdoor inspection on a cold day (ambient 5°C), which parameters must the thermographer enter to ensure accurate temperature measurement?
Question · Easy
Black electrical tape of emissivity 0.95 is applied to a painted pipe and allowed to equilibrate. With the camera emissivity set to 0.95 the tape reads 51°C and the adjacent bare paint reads 48°C. What is the correct next step to find the paint emissivity?
1.2 Level I vs Level II Scope and Prerequisites
ISO 18434-1 governs infrared thermography within machinery condition monitoring. What does it provide for judging the severity of a hot bearing housing?
A thermographer compares two images of the same circuit breaker taken six months apart. The first shows a 4°C difference against a similar breaker; the current image shows 12°C under the same load. The BEST interpretation is:
Trending Baseline Comparison
What is the primary purpose of establishing a thermal baseline for electrical switchgear?
Which of the following emissivity values is MOST accurate for polished stainless steel?
Chapter 2: Thermometry Fundamentals
2.1 Temperature Scales and Conversions
During a building envelope inspection a thermographer observes a cold spot on an interior wall. Under ASTM C1060, the suggested minimum interior-to-exterior temperature difference to hold for four hours before the inspection is:
A Level II thermographer reviewing work from a Level I inspector notices the Level I used an emissivity of 0.95 for a copper bus bar and reported a temperature of 74°C. The actual emissivity of the oxidized copper bar is 0.40. What action should the Level II take?
Qa Qc Level I
The Stefan-Boltzmann law underlies quantitative IR thermography. Which statement BEST describes its relevance to emissivity correction?
A thermographer applies black paint to a small area of a motor housing to use as an emissivity reference. After temperature equilibration, the paint area reads 62°C. The unpainted area reads 58°C with the camera set to the paint emissivity (0.95). What is the most likely explanation?
2.2 Contact vs Non-Contact Thermometers
For a flat roof inspection using IR thermography, which environmental condition would MOST interfere with the ability to detect wet insulation?
For an ASTM C1060 thermographic inspection of insulation in frame wall cavities, which inspection mode is preferred for detecting missing insulation?
A Level II thermographer is reviewing a thermal image of a three-phase motor. One phase shows a significantly higher temperature than the other two phases under similar loading. The MOST likely interpretation is:
Data Analysis
Under ANSI/NETA Table 100.18, a component measured 30°C above the ambient air temperature falls in which recommended-action band?
2.3 Identifying and Reducing Measurement Errors
When performing quantitative temperature measurement through an IR window with 93% transmittance, the thermographer sets the camera transmittance to 0.93. What additional parameter adjustment is required?
What emissivity value should be used when measuring the temperature of still water or a water-based surface using a longwave IR camera (8–14 µm)?
A thermal image shows a uniform hot pattern across the entire surface of a three-phase transformer. This pattern is MOST consistent with:
Which of the following is a key QA/QC responsibility of a Level II thermographer when reviewing Level I inspection data?
Chapter 3: Thermal Science and Heat Transfer
3.1 Thermal Science: Temperature, Energy Units, and Heat Capacity
A thermographer inspecting a fuse block finds one fuse at 45°C while adjacent identical fuses under the same load read 28°C. Applying the similar-components column of ANSI/NETA Table 100.18, this 17°C difference calls for:
What is the recommended minimum load level for meaningful electrical IR inspections per industry standards?
A Level II thermographer must write a finding report for a medium-voltage switchgear anomaly. Which element is REQUIRED in a technically complete IR inspection report?
Reporting Standards
Which emissivity value is MOST accurate for heavily oxidized carbon steel at temperatures above 200°C?
3.2 Heat Transfer Modes and Conduction Variables
An opaque surface has an emissivity of 0.65. In the camera's radiometric equation, what fraction of the background radiation falling on that surface is reflected back toward the camera?
During a mechanical inspection, a bearing housing shows a temperature of 72°C with a baseline from six months ago of 55°C. Load and ambient conditions are identical. The rate of temperature rise is most concerning if:
Which of the following materials has an emissivity closest to 0.95 and requires the LEAST emissivity correction for accurate temperature measurement?
A thermographer inspects overhead power lines from a safe distance of 15 metres. Which parameter matters far more here than it would during a 1 metre indoor inspection?
Chapter 4: Advanced Infrared Theory
4.1 Radiant Power and Stefan-Boltzmann Law
A Level II thermographer receives thermal images of motor stator windings captured by a Level I inspector. The images show the emissivity was set to 0.95 for varnish-coated copper windings. The Level II determines this is:
ISO 18434-1 describes comparative thermography. What is the recommended way to assess bearing temperatures on two identical machines running under identical conditions?
A thermographer detects a hot spot on a 480V motor control center bus bar, but the load is only 18% of rated. The ΔT compared to adjacent bus bars is 9°C. What is the BEST action?
What is the purpose of the 'reflected apparent temperature' (RAT) measurement in quantitative IR thermography?
4.2 Planck's Curves and Wien's Displacement Law
An IR inspection report on electrical equipment must document load conditions at the time of inspection because:
A thermographer inspecting a high-voltage substation measures a suspension insulator string. One insulator disk shows a uniformly cool pattern compared to adjacent disks under voltage stress. This is MOST consistent with:
Which of the following scenarios would produce the MOST accurate temperature measurement using a non-contact IR camera?
A thermographer discovers a Level I inspector reported a 25°C temperature differential on a circuit breaker but failed to note the load at the time of inspection. What is the Level II's appropriate response?