9.3 Clause 8 — Inspection and Acceptance Criteria

Key Takeaways

  • Table 8.1 is the most important acceptance criteria table — different limits for static vs. cyclic loading
  • Cracks are NEVER permitted in any structure (static or cyclic) per AWS D1.1
  • Undercut limits: ≤ 1/32" (statically loaded), ≤ 0.01" (cyclically loaded)
  • VT is required on 100% of all welds; RT/UT required for specified CJP groove welds
  • NDT personnel must hold ASNT certification (2025 edition requirement)
  • Repairs must be re-inspected using the same NDE method(s) as the original inspection
Last updated: March 2026

9.3 Clause 8 — Inspection and Acceptance Criteria

Clause 8 of AWS D1.1 defines the inspection requirements and acceptance criteria for structural steel welds. This is the most frequently referenced clause during actual CWI work and on Part C of the exam.

Inspector Qualifications (Clause 8 Requirements)

AWS D1.1:2025 requires:

  • Visual inspection shall be performed by a CWI, SCWI, or CAWI (under CWI supervision) qualified per AWS QC1
  • NDT personnel shall hold ASNT certification (new requirement in 2025 edition — eliminates ambiguity)
  • The contractor shall provide the inspector with access and assistance

Visual Inspection Acceptance Criteria — Table 8.1

Table 8.1 is the most important table for CWI practice. It provides different acceptance criteria based on:

  • Type of loading: Statically loaded vs. cyclically loaded
  • Type of structure: Nontubular vs. tubular

Key Visual Acceptance Criteria (Nontubular — Summary):

DiscontinuityStatically LoadedCyclically Loaded
CracksNot permittedNot permitted
Incomplete fusionNot permittedNot permitted
Crater cross sectionMust be filled to full cross sectionMust be filled to full cross section
Weld profilesPer Figure 7.1Per Figure 7.1
Undercut≤ 1/32" for any weld length (with exceptions up to 1/16" in isolated spots)≤ 0.01"
PorosityVarious limits by type (piping, scattered)More restrictive than static
Weld sizeEqual to or greater than specified (with tolerances)Equal to or greater than specified

NDE Requirements

AWS D1.1 specifies when NDE beyond VT is required:

NDE MethodWhen Required
VTAll welds (100%) — always required
RT or UTCJP groove welds in cyclically loaded structures (extent per contract); specified joints per Engineer
MT or PTWhen specified by contract documents or Engineer

UT Acceptance Criteria — Table 8.2

For welds examined by ultrasonic testing, Table 8.2 provides acceptance criteria based on:

  • Weld thickness
  • Indication rating (dB)
  • Flaw length
  • Flaw class (Class A through D, with Class A being most restrictive)

RT Acceptance Criteria

Clause 8 references acceptance criteria for RT that evaluate:

  • Elongated indications (slag, lack of fusion) — limited by length and cumulative length
  • Rounded indications (porosity) — limited by size and distribution charts
  • Cracks — not permitted regardless of size

Repair Requirements

When a weld is rejected:

  1. The area of rejection must be clearly marked
  2. The CWI documents the rejection and required repair
  3. Repairs must be performed per an approved WPS
  4. Re-inspection of the repair must be performed using the same NDE methods as the original inspection
  5. If repair is performed by air carbon arc gouging, the gouged area must be ground smooth before re-welding

2025 Edition Key Changes

ChangeImpact
NDT personnel must hold ASNT certificationEliminates ambiguity about qualification standards
Table 8.1 undercut limits updatedTied to weld length and base-metal thickness
Preheat/interpass temperature now mandatory on WPSClause 6 change — but affects inspection verification
New Table 5.2 organizationEssential variables reorganized for WPS writing clarity

For the Exam: Table 8.1 is the most tested table on Part C. Know the key differences between statically loaded and cyclically loaded acceptance criteria — especially for undercut (1/32" vs. 0.01") and cracks (never permitted in either case).

Test Your Knowledge

Per AWS D1.1 Table 8.1, are cracks permitted in statically loaded structures?

A
B
C
D
Test Your Knowledge

Per AWS D1.1:2025, what certification must NDT personnel hold?

A
B
C
D
Test Your Knowledge

After a weld is rejected, the repair must be re-inspected using:

A
B
C
D